Siemens simatic hmi op27 Equipment Manual page 193

Operator panels
Table of Contents

Advertisement

Technical Data
Control Panel Interface
Voltage supply for outputs, load voltage supply and internal logic circuitry
Voltage supply
S
rated value
S
permissible range
S
value at t < 0.5 sec
Power consumption of logic circuitry
Short-circuit protection upon polarity rever-
sal of load voltage
Connection of
Outputs
No. of outputs
S
in groups of
S
output DO1 to DO4
S
output DO5 to DO8
S
output DO9 to DO12
S
output DO13 to DO16
Optical isolation
Output voltage
S
with signal "0"
S
with signal "1"
Output current
S
with signal "0"
S
with signal "1"
Switch rate at
S
resistive load
S
lamp load
Load current per group
S
aggregate current
S
on short-circuit
Cable length
Voltage supply for inputs
Voltage supply
S
rated value
S
permissible range
S
value at t < 0.5 sec
Connection of
A-4
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
OP27
+ 24 V DC
+18.0 to +30.0 V
35 V
40 mA
4
Lamps (inductive load not permitted)
16
4
Group 1
Group 2
Group 3
Group 4
Max. 2 V (idling)
Min. (voltage supply –3 V)
Max. 1 mA
Max. 500 mA per group
1 output of 200 mA, the remainder 100 mA
Max. 100 Hz
Max. 8 Hz
500 mA
Complete group deenergized
Max. 1 m
+ 24 V DC
+18.0 to +30.0 V
35 V
Pushbuttons, switches (inductive load not permitted)
OP27, OP37 Equipment Manual
OP37
Release 05/99

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic hmi op37

Table of Contents