Restore firmware/
Perform the following steps to load a backup of the firmware/configuration
configuration
onto the OP:
Automatic
If the function Backup/Restore is added to the insertion point "Initialization" in
restoring of
the configuration, the function is called in each time the OP is started up, being
firmware/
loaded from the memory card. The system then asks whether the internal flash
configuration
memory should be overwritten by the data stored on the memory card.
OP27, OP37 Equipment Manual
Release 05/99
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Step
1
Insert the memory card containing the firmware/configuration in Slot A of
the OP27 or Slot B of the OP37.
2
Restart the OP. The OP is then started up with the firmware/configuration
contained on the memory card.
3
Press the function key, depicted on the right, in the Backup/Re-
store standard screen to call in the Restore function.
The memory contents of the internal flash memory are over-
written by the firmware/configuration contained on the memory
card.
4
Remove the memory card from the OP.
Step
1
Insert the memory card containing the backup into the corresponding slot
of the system.
2
Start the OP.
3
Confirm initiation of the restore function by answering "OK" at the
prompt.
4
Remove the memory card from the OP.
Storing and Loading Data
Action
Action
9-7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic hmi op37