Advertisement

5.16

Meter setting and adjustment

• Function
Inverter's operation data is sent to the FM terminal (AM terminal) as analog voltage signals or analog current
signals. To display inverter's operation data, connect a meter to this terminal. The "FM terminal-connected meter
adjustment
Note 1: The signal output from the FM and AM terminal is an analog voltage signal or an analog current signal.
(positive (+) side output. For signed data, an absolute value is output. To output data with positive and
negative sings, you need to use two extended terminal boards (optional).)
Note 2: To the FM terminal, connect either a full-scale 0~1mAdc ammeter or a full-scale 0~7.5Vdc (or 10Vdc)
5
voltmeter, if necessary. The FM terminal can also be used as a 0(4)~20mAdc output terminal.
To the AM terminal, connect either a full-scale 0~1mAdc ammeter or a full-scale 0~7.5Vdc (or 10Vdc)
voltmeter, if necessary.
Connect meters as shown below.
<Connection to terminal FM>
VF-PS1
A frequency meter QS60T is optionally available.
Output modes of the FM terminal
When used with a 0~1mAdc ammeter
(Default setting)
When the optional frequency meter QS60T is
connected, this mode is selected.
<Connection to terminal AM >
VF-PS1
It is recommendable to use an ammeter with a current rating 1.5 or more times as high as the output current
rating of the inverter.
: FM terminal meter selection
: FM terminal meter adjustment
: Constant at the time of filtering
: FM voltage/current output
switching
: Inclination characteristic of FM
output
: FM bias adjustment
" (AM terminal-connected meter adjustment
+
FM
-
CCA
The reading of the frequency meter fluctuates during calibration.
When used with a DC0~10V voltmeter
FM
0-10V
0-1mA
0-20mA
SW2
+
AM
-
CCA
The reading of the ammeter fluctuates during calibration.
: FM output filter
: AM terminal meter
selection
: AM terminal meter
adjustment
: Inclination characteristic
of AM output
: AM bias adjustment
) parameter is used to calibrate the
Meter: Frequency meter
(default setting)
FM
0-10V
0-1mA
0-20mA
SW2
=
Meter: Ammeter
(default setting)
E-26
E6581531
meter.
When used with a 0(4)~20mAdc
FM
0-10V
0-1mA
0-20mA
SW2
=