6.3.3 Modifying output terminal functions

⇒ For details, refer to Section 7.2.2.
6.4

Basic parameters 2

6.4.1 Switching among V/f characteristics 1 and 2 from input terminal

• Function
Use the above parameters to switch the operation of 2 motors with a single inverter and to select motor V/f
characteristics (1 to 2) according to the particular needs or operation mode.
[Switching methods]
6
Terminals are used for this switching.
Note: The setting of parameter
selected, V/f control is performed in constant torque mode. Do not switch motors when the parameter
(1 to 2), refer to table on the next page.
Note: Refer to Section 5. 8
Section 5. 8
Section 5.7
and Section 5.14
: Output terminal function selection 1 (OUT1)
: Output terminal function selection 2 (OUT2)
: Output terminal function selection 3 (FL)
~
: Output terminal function selection 4~9
~
: Output terminal function selection 10, 11
: Base frequency 2
: Base frequency voltage 2
: Manual torque boost 2
: Thermal protection level 2
(V/f control mode selection) is valid only when V/f1 is selected. If V/f2 is
(V/f control mode selection) is set at
(Base frequency 1) for
(Base frequency voltage 1) for
(Manual torque boost) for
(Motor electronic thermal protection level 1) for
. For parameters selected when changing V/f characteristics
,
,
,
F-8
E6581531
, respectively.