Low Torque Detection Signals - Toshiba TOSVERT VF-PS1 Instruction Manual

High performance inverter
Hide thumbs Also See for TOSVERT VF-PS1:
Table of Contents

Advertisement

6.28

Low torque detection signals

: Undertorque detection selection
: Undertorque detection level during power running
: Undertorque detection level during regenerative braking
: Undertorque detection time
: Undertorque detection hysteresis
• Function
If the torque remains below the level specified with
specified with
= : Alarm signal output (No tripping)
With an output terminal function selection parameter, the inverter can be set so as to issue an
undertorque alarm.
The output terminal function number is 142 or 143 (reverse video).
= : Trip signal output
If the torque is found to be below the value set with
with
Title
Undertorque detection selection
Undertorque detection level during
power running
Undertorque detection level during
regenerative braking
Undertorque detection time
Undertorque detection hysteresis
<Example of operation>
Output terminal function: 142 (Low torque detection )
=
(Alarm output)
Ex.) When outputting low torque detection signals through output terminal OUT1
Title
Output terminal function selection 1(OUT1)
Note: To put out signals to the terminal OUT2, select the parameter
Low torque
signal output
Output torque [%]
+
When
After tripping, the low torque signal remains ON.
, the inverter will be tripped. Then the trip message "
, the inverter will be tripped. (FL activated under a fault signal)
Function
Function
=
(tripping), the inverter will trip if low torque lasts for the period of time set with
F-59
or
for a period longer than that
" appears.
or
Adjustment range
: Alarm mode
: Trip mode
~
%
~
%
~
sec.
~
%
Adjustment range
~
.
OFF
less than
Time [sec]
E6581531
for a period longer than that set
Default setting
Example of setting
ON
OFF
.
6