2.3
Description of terminals
2.3.1 Main circuit terminals
This diagram shows an example of wiring of the main circuit. Use options if necessary.
Power supply and motor connections
Power supply
2
Connection with peripheral equipment
Molded-case
circuit breaker
Power
supply
Main circuit
Terminal symbol
R/L1, S/L2, T/L3
(R/L1.1, S/L2.1, T/L3.1,
R/L1.2, S/L2.2, T/L3.2)
*1
U/T1, V/T2, W/T3
PA/+, PB
(PA, PB) *2
PC/-
PO, PA/+
RO, SO, TO
*1: Value in ( ) VFPS1-6500KPC to 6630KPC.
*2: Value in ( ) VFPS1-6110KPC to 6200KPC.
Connect the power
cables to RL1, S/L2,
and T/L3.
R/L1
S/L2
Molded-case
circuit
breaker
High-attenuation
Input AC
radio noise
Magnetic
contactor
reactor
reduction filter
Simplified
radio noise
filter
Grounding terminal for inverter casing
Power input terminal
VFPS1-5022PM~5075PM:
Three-phase 500~600V-50/60Hz
Connect to a (3-phase induction) motor.
Connect a braking resistor.
Change the parameters
250kW models and larger are not equipped with terminal PB.
This is a negative potential terminal in the internal DC main circuit.
Shorted by a short bar when shipped from the factory (90kW or smaller).
VFPS1-6110KPC or larger
Inverter's cooling fan power input terminals. Don't need to connect if you use TRS.
(TRS: Transformer for fan supply)
VF-PS1
Connect the motor
cables to U/T1, V/T2
and W/T3.
T/L3
U/T1 V/T2 W/T3
Inverter
U/T1
R/L1
S/L2
V/T2
W/T3
T/L3
PA/+ P0
PA PB
Braking resistor [Note]
Terminal function
VFPS1-6030PL~6630KPC:
Three-phase 500~690V-50Hz/60Hz
,
and
if necessary.
B-10
E6581531
Motor
E
Surge
suppressing filter
Motor
IM
Zero-phase
reactor
Note: Connect a braking unit
between the terminals PA/+
and PC/-, if necessary.