Honeywell OMNI 408 Installation And Setup Manual page 11

Fbii hardwired/wireless system
Table of Contents

Advertisement

TERMINALS
FUNCTION
RF Zone
Zone
Interface
Information
(wireless
zones)
15 (Black),
Keypads
16 (Yellow),
17 (Green),
18 (Red)
19 (Brown),
Telephone
20 (Gray),
Line
21 (Green),
22 (Red)
Normally-closed devices may be wired in series; normally-open devices
may be wired in parallel. A 2.2k-ohm end-of-line resistor must be installed
on all zones even when using zones 1–4 as wireless. (Refer to the wiring
diagram.) The standard loop response time is 280 ms on all zones. The
factory default values for each zone are listed in the table above; however,
any zone can be programmed for the following types: delay, perimeter,
interior, fire, 24-hr. alarm, or 24-hr. trouble. See further explanation of the
zone types in Section 9 : System Programming .
NOTE: Loop response is defined as the minimum time required for a fault
to trip a zone.
Zone 5 (Compatible RF Devices) [Default = Perimeter]
Zone 6 (Compatible RF Devices) [Default = Perimeter)
Zone 7 (Compatible RF Devices) [Default = Perimeter]
Zone 8 (Compatible RF Devices) [Default = Perimeter]
Wireless zones can be enabled in Program Question 26, Locations 1 and
2. All 8 zones can be wireless; or up to 4 zones can be hardwired and the
remaining ones wireless. Compatible ADEMCO 5800 Series wireless
devices must be used.
Up to 4 keypads may be wired to these terminals. The connections are as
follows: 15 (Black) = negative, 16 (Yellow) = data in, 17 (Green) = data
out, and 18 (Red) = positive power. Maximum keypad length is 500 feet
using 22-gauge wire.
NOTE: In some installations, it may be necessary to use shielded wire to
prevent radio frequency interference.
Connect the RJ31X cord as follows: 19 (Brown) = Home Tip, 20 (Gray) =
Home Ring, 21 (Green) = Telco Tip, and 22 (Red) = Telco Ring. Insert the
plug into a USOC RJ31X jack (or a CA31A jack for Canadian installations).
The FCC registration number is 5GBUSA-4403-AL-E, and the ringer
equivalence is 0.1B. The system should not be connected to party lines or
coin-operated phones.
If this control panel will be used for uploading, downloading, or remote-
command applications, the telephone line connected to the control panel
must not be shared with a fax machine or modem. Furthermore, this
device should not be connected to a phone line that has Call Waiting,
unless the Call Waiting Interrupt numbers are programmed into the panel
dialing sequence.
Section 2 - System Wiring and Hookup
DESCRIPTION
2–3