Technical data

12.3 EMC requirements

12.3
EMC requirements
EMC requirements
Compliance of the named products with the regulations of Directive 89/336 EEC is verified
by conformance with the following standards:
Noise immunity
Static discharge (contact discharge/air
discharge)
RF irradiation
Pulse modulation
RF conduction
Burst interference
Supply lines
Process data lines
Signal lines
Surge coupling
Power supply cable
Magnetic fields
Radio interference
Radio interference level complying to EN 55011
12-8
Norms
EN 61000-4-2
EN 61000-4-3
EN 61000-4-3
EN 61000-4-6
EN 61000-4-4
EN 61000-4-5
EN 61000-4-8
Class A
6 kV/8 kV
10 V/m, 80% AM,
1 kHz
900 MHz ±5 MHz
10 V/m
eff.
150 kHz - 80 MHz
10 V, 80% AM, 1 kHz
2 kV
2 kV
1 kV
1 kV with choke,
Type DEHNrail (Order No. 901 104)
2 kV with choke,
Type DEHNrail (Order No. 901 104)
30A/m 50/60 Hz
TP 270, OP 270, MP 270B (WinCC flexible)
Operating Instructions, Edition 03/2004, 6AV6691-1DD01-0AB0
, 50% ED, 200 Hz