IVT 09LR-N Service Manual page 39

Split type air to air heat pump
Table of Contents

Advertisement

Problem
Outdoor
symptom
unit indi-
cation
(LED1)
Indoor and
8-time
     Timer (Orange)
outdoor units
do not oper-
ate.
Indoor and
9-time
     Timer (Orange)
outdoor units
do not oper-
ate.
Indoor and
     Timer (Orange)
outdoor units
do not oper-
ate.
Indoor and
10-time      Timer (Orange)
outdoor units
do not oper-
ate.
Indoor and
     Timer (Orange)
outdoor units
do not oper-
ate.
Indoor and
     Timer (Orange)
outdoor units
do not oper-
ate.
Indoor unit
Malfunc-
tion No.
Lamp
Main Sub
8
0
Operation (Red)
Plasmacluster
(Blue)
9
0
 Operation (Red)
Plasmacluster
(Blue)
4
 Operation (Red)
Plasmacluster
(Blue)
10
0
Operation (Red)
Plasmacluster
(Blue)
1
Operation (Red)
Plasmacluster
(Blue)
2
Operation (Red)
Plasmacluster
(Blue)
Content of diagnosis
Main
Sub
Abnormal
Abnormal wire
wire check
check error
Cycle tem-
Thermisttor
perature
installtion error or
4-way valve
error.
4 way valve error
or Gas leak error
EEPROM
EEPROM (out-
error
door) data error
EEPROM (out-
door) data error
CPU (outdoor)
RAM data error
3 – 17
Check point
(1) Check the expansion
(1) Replace the out-
valve. (unit A - C)
door control board
assembly.
(2) Are four expansion
(2) Reattach
valves connected by
mistake
(3) Check the wiring
(3) Check the wiring
between units.
between units.
(1) Check the ther-
(1) Correct the instal-
mistor (heat
lation.
exchanger) and (2-
way valve) are
installed in correct
positions.
(2) Check if the refriger-
(2) Change the speci-
ant volume is abnor-
fied amount of
mally low.
refrigerant.
(3) Check the 4-way
(3) Replace the 4-way
valve for proper
valve.
operation.
(4) No abnormalyty
(4) Replace the out-
found in above
door unit control
inspections (1) thro-
PCB assembly.
hgh (3).
(1) Check the ther-
(1) Correct the instal-
mistor indoor/out-
lation.
door exchange are
installed in correct
portions.
(2) Check if the refriger-
(2) Change the speci-
ant volume is abnor-
fied amount of
mally low.
refrigerant.
(3) Check the 4-way
(3) Replace the 4-way
valve for proper
valve.
operation.
-
(1) Replace the out-
door unit control
PCB assembly.
12LRN
Action