IVT 09LR-N Service Manual page 24

Split type air to air heat pump
Table of Contents

Advertisement

12LRN
Function
10 AC overcurrent error
Indoor and outdoor units stop if out-
in compressor OFF
door AC current exceeds about 3 A
status
while compressor is in non-opera-
tion status.
11
AC maximum current
Compressor stops if coutdoor AC
error
current exceeds 17 A.
12 AC current defi-
Compressor stops if operating fre-
ciency error
quency is 50 Hz or higher and out-
door AC current is about 2.0 A or
lower.
13 Thermistor installa-
Compressor stops if high and low
tion error or 4-way
values of temperatures detected by
valve error
outdoor unit heat exchanger ther-
mistor (TH2) and 2-way valve ther-
mistor (TH5) do not match
operating cycle.
14 Compressor high
Compressor stops if compressor
temperature error
chamber thermistor (TH1) exceeds
about 114C, or if there is short-cir-
cuit in TH1.
15 Outdoor unit heat
Compressor stops if there is short-
exchanger thermistor
circuit in outdoor unit heat
short-circuit error
exchanger thermistor (TH2).
16 Outdoor unit outside
Compressor stops if there is short-
air temperature ther-
circuit in outdoor unit outside air
mistor short-circuit
temperature thermistor (TH3).
error
17 Outdoor unit suction
Compressor stops if there is short-
thermistor short-cir-
circuit in outdoor unit suction ther-
cuit error
mistor (TH4).
18 Outdoor unit 2-way
Compressor stops if there is short-
valve thermistor
circuit in outdoor unit 2-way valve
short-circuit error
thermistor (TH5).
19 Outdoor unit heat
Compressor stops if there is open-
exchanger thermistor
circuit in outdoor unit heat
open-circuit error
exchanger thermistor (TH2).
20 Outdoor unit outside
Compressor stops if there is open-
air temperature ther-
circuit in outdoor unit outside air
mistor open-circuit
temperature thermistor (TH3).
error
21 Outdoor unit suction
Compressor stops if there is open-
thermistor open-cir-
circuit in outdoor unit suction ther-
cuit error
mistor (TH4).
22 Outdoor unit 2-way
Compressor stops if there is open-
valve thermistor
circuit in outdoor unit 2-way valve
open-circuit error
thermistor (TH5).
23 Outdoor unit dis-
Compressor stops if there is open-
charge thermistor
circuit in outdoor unit discharge
open-circuit error
thermistor (TH1).
24 Serial signal error
Compressor stops if outdoor unit
cannot receive serial signal from
indoor unit for 30 seconds.
25 Compressor startup
Compressor stops if compressor
error
fails to start up.
26 Compressor rotation
Compressor stops if there is no
error (at 120 ener-
input of position detection signal
gizing)
from compressor or input is abnor-
mal.
27 Outdoor unit DC fan
Operation stops if there is no input
error
of rotation pulse signal from out-
door unit fan motor for 30 seconds.
28 PAM overvoltage
Compressor stops if DC voltage is
error
400 V or higher.
Operation
Description
Detection period
When compressor is in
non-operation
When compressor is in
operation
When compressor is in
operation
3 minutes after com-
pressor startup
When in operation
At compressor startup Operation OFF or ON Yes ✩1
At compressor startup Operation OFF or ON Yes ✩1
At compressor startup Operation OFF or ON Yes ✩1
At compressor startup Operation OFF or ON Yes ✩1
At compressor startup Operation OFF or ON Yes ✩1
At compressor startup Operation OFF or ON Yes ✩1
At compressor startup Operation OFF or ON Yes ✩1
At compressor startup Operation OFF or ON Yes ✩1
At compressor startup Operation OFF or ON Yes ✩1
When in operation
At compressor startup Operation OFF or ON Yes ✩3
Compressor operating
at 120 energizing
When outdoor unit fan
is in operation
When in operation
Reset condition
Replacement of defec-
tive parts such as IPM
Operation OFF or ON Yes ✩1
Operation OFF or ON Yes ✩1
Operation OFF or ON Yes ✩1
Operation OFF or ON Yes ✩1
Reset after reception of
serial signal
Operation OFF or ON Yes ✩3
Operation OFF or ON Yes ✩1
Operation OFF or ON Yes ✩1
3 – 2
Self-diagnosis result
display
Indoor
Indoor
Outdoor
unit error
unit
unit
display
Yes ✩2
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
None
None
None
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes