CHAPTER 3.
12LRN
FUNCTION AND OPERATION OF PROTECTIVE PROCEDURES
[1] PROTECTION DEVICE FUNCTIONS AND OPERATIONS
Function
1
Indoor unit fan lock
Operation stops if there is no input
of rotation pulse signal from indoor
unit fan motor for 1 minute.
Indoor unit fan rota-
Operation stops if rotation pulse
tion speed error
signal from indoor unit fan indicates
abnormally low speed (about 300
rpm or slower).
2
Indoor unit freeze
Compressor stops if temperature
prevention
remains below 0C for 4 minutes.
3
2-way valve freeze
Compressor stops if temperature of
prevention
outdoor unit 2-way valve remains
below 0C for 10 continuous min-
utes during cooling or dehumidify-
ing operation.
4
Indoor unit heat
Operating frequency lowers if
exchanger overheat
indoor unit heat exchanger temper-
shutdown
ature exceeds overheat tempera-
ture during heating operation.
Compressor stops if indoor unit
heat exchanger temperature
exceeds overheat temperature for
60 seconds at minimum frequency.
Overheat temperature setting value
indoor unit heat exchanger ther-
mistor temperature: about 45 to
54C
5
Outdoor unit heat
Operation frequency lowers if out-
exchanger overheat
door unit heat exchanger tempera-
shutdown
ture exceeds about 55C during
cooling operation.
Compressor stops if outdoor unit
heat exchanger temperature
exceeds about 55C for 120 sec-
onds at minimum frequency.
6
Compressor dis-
Operating frequency lowers if tem-
charge overheat shut-
perature of compressor chamber
down
thermistor (TH1) falls below about
110C.
Compressor stops if temperature of
compressor chamber thermistor
(TH1) remains at about 110C (for
120 seconds in cooling operation,
or 60 seconds in heating operation)
at minimum frequency.
7
Dehumidifying opera-
Compressor stops if outside air
tion temporary stop
temperature thermistor is lower
than about 16C during dehumidify-
ing operation.
8
DC overcurrent error Compressor stops if DC current of
about 25 A or higher flows in IPM.
9
AC overcurrent error Operating frequency lowers if out-
door AC current exceeds peak con-
trol current value. outdoor stops if
compressor AC current exceeds
peak control current value at mini-
mum frequency.
Operation
Description
Detection period
When indoor unit fan is
in operation
When indoor unit fan is
in operation
When in cooling or
dehumidifying opera-
tion
When in cooling or
dehumidifying opera-
tion
When in heating opera-
tion
When in cooling or
dehumidifying opera-
tion
When compressor is in
operation
When in dehumidifying
operation
When compressor is in
operation
When compressor is in
operation
Service Manual
Reset condition
Operation OFF or ON ✩2
Operation OFF or ON ✩2
Automatic reset when
heat exchanger tem-
perature rises above
freeze prevention tem-
perature (2C or
higher)
Automatic reset when
temperature of 2-way
valve rises above
10C.
Automatic reset after
safety period (180 sec).
Automatic reset after
safety period (180 sec).
Automatic reset after
safety period (180 sec).
Automatic reset when
outside air tempera-
ture rises above 16C.
Operation OFF or ON Yes ✩1
Operation OFF or ON Yes ✩1
3 – 1
12LRN
Self-diagnosis result
display
Indoor
Indoor
Outdoor
unit error
unit
unit
display
Yes
None
Yes
None
None
None
None
Yes
Yes
None
Yes
Yes
None
Yes
Yes
None
Yes
Yes
None
Yes
Yes
Yes
Yes
Yes
Yes