TCN-890x Electronic Room Thermostats
Installation
Install the TCN-890x where the occupant can read and
adjust the setpoint dial selector easily. Situate the
module where the temperature is representative of the
general room conditions. Avoid installing the
TCN-890x near cold or warm air drafts, radiant heat, or
direct sunlight.
IMPORTANT:
The TCN-8900 Series electronic
room thermostats are intended to control equipment
under normal operating conditions. Where failure or
malfunction of the TCN-890x thermostat could lead
to an abnormal operating condition that could cause
personal injury or damage to the equipment or other
property, other devices (limit or safety controls) or
systems (alarm or supervisory) intended to warn of,
or protect against, failure or malfunction of the
TCN-890x thermostat must be incorporated into and
maintained as part of the control system.
IMPORTANT:
Do not mount the module on an
exterior wall. Make all wiring connections in
accordance with the National Electrical Code and all
local regulations.
Parts Included
TCN-890x electronic room thermostat with
attached surface mount base
U.S. wallbox mounting base
endcaps (2)
plastic wall anchors (2)
No. 8 x 1-1/4 in. slotted pan-head thread-forming
screws (2)
No. 6-32 x 1 in. flat-head machine screws (2)
© 2002 Johnson Controls, Inc.
24-9733-18
Part No.
, Rev. —
Installation Instructions TCN-890x
Dimensions
For TCN-890x thermostat dimensions, refer to
Figure 1, Figure 2, and Figure 3.
3.15 (80)
65
70
20
75
60
16
24
3.15
(80)
55
80
12
28
C
F
Figure 1: TCN-890x-2161 Cover Dimensions,
in. (mm)
1 2 3
4
5
6
Figure 2: TCN-890x Surface Mount Base
Dimensions, in. (mm)
Issue Date May 1, 2002
1.29 (33)
Setpoint
Dial
Temperature
Scale
7 8 9
10
11 12
www.johnsoncontrols.com
1

Advertisement

loading

Summary of Contents for Johnson Controls TCN-890x

  • Page 1 Situate the module where the temperature is representative of the 3.15 (80) 1.29 (33) general room conditions. Avoid installing the TCN-890x near cold or warm air drafts, radiant heat, or direct sunlight. IMPORTANT: The TCN-8900 Series electronic Setpoint room thermostats are intended to control equipment 3.15...
  • Page 2 Figure 3: TCN-890x Wallplate Dimensions, in. (mm) Kit to help reduce drafts entering the unit. Drafts can result in false temperature readings. Mounting The TCN-890x thermostat can be either surface or 1. Wire to appropriate terminals as described in the wallbox mounted. Wiring section.
  • Page 3 Mount Base Wallbox Mounting Figure 8: Removing the Terminal Blocks from the To mount the TCN-890x on a standard 2 x 4 in. Surface Mounting Base [51 x 102 mm] U.S. wallbox: 6. Proceed to the Wiring section before mounting the 1.
  • Page 4 Reassembling the Wallbox-Mounted TCN-890x To replace the TCN-890x cover onto the installed IMPORTANT: All wiring to the thermostat is wallbox mounting base: low voltage (Class 2) and must be separated from the power line voltage wiring. Do not run wiring close 1.
  • Page 5: Setup And Adjustments

    PB/RA potentiometer controls the proportional adjustment to the RA output, Terminal 3 (Heating) • the PB/DA potentiometer controls the proportional adjustment to the DA output, Terminal 5 (Cooling) Figure 14: TCN-8901 PCB with Potentiometers TCN-890x Electronic Room Thermostats Installation Instructions...
  • Page 6: Compliance Statements

    Reverse Acting (RA) and Direct Acting (DA) Unoccupied Mode Outputs In the TCN-890x, the Unoccupied Mode offsets the All TCN-890x thermostats provide two outputs for setpoint by 9F° (5C°). (See Figure 16 and Figure 17.) applications using separate heating or cooling The setpoint is decreased for the RA (heating) output actuators.
  • Page 7 DA Output (Cooling) Figure 16: TCN-8901 0 to 10 VDC Control Sequence Unoccupied Offset Unoccupied Offset Output Temperature Setpoint Unoccupied Occupied Occupied Unoccupied RA Output (Heating) DA Output (Cooling) Figure 17: TCN-8906 On/Off Control Sequence TCN-890x Electronic Room Thermostats Installation Instructions...
  • Page 8: Technical Specifications

    The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.