Connect Dc Power To A Dc-Powered Acx1000 Or Acx1100 Router - Juniper ACX1100 Quick Start Manual

Universal access router
Hide thumbs Also See for ACX1100:
Table of Contents

Advertisement

Connect DC Power to a DC-Powered ACX1000 or ACX1100 Router

Copyright © 2015, Juniper Networks, Inc.
To connect power to the DC-powered router, you need the following tools:
Phillips (+) screwdriver, number 2
ESD grounding wrist strap
M3 screws and flat washers
DC power source cables, minimum 14 AWG or as required by local code (not provided)
Ring lugs, Molex 190700067 or equivalent (not provided)
The DC power supply has four terminals on the front panel, covered by a clear plastic
cover.
Table 1: ACX Series DC Power System Input Voltage
Nominal Voltage
+24
–48
–60
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist, and connect
1.
the strap to one of the ESD points on the chassis. For more information about ESD,
see the
ACX1000 and ACX1100 Universal Access Routers Hardware Guide
Switch off the dedicated customer site circuit breakers. Ensure that the voltage across
2.
the DC power source cable leads is 0 V and that there is no chance that the cable
leads might become active during installation.
Remove the clear plastic cover protecting the terminal on the faceplate.
3.
Verify that the DC power cables are correctly labeled before making connections to
4.
the power supply. In a typical power distribution scheme where the return is connected
to chassis ground at the battery plant, you can use a multimeter to verify the resistance
of the –48V and return DC cables to chassis ground:
For –48V and –60V:
a. The cable with very large resistance (indicating an open circuit) to chassis ground
is the DC input cable (
b. The cable with very low resistance (indicating a closed circuit) to chassis ground
is the return cable (
+
For +24V:
a. The cable with very low resistance (indicating a closed circuit) to chassis ground
is the DC input cable (
Connect DC Power to a DC-Powered ACX1000 or ACX1100 Router
Specification
Operating range: +18 to +30 VDC
Operating range: –39 to –56 VDC
Operating range: –39 to –72 VDC
).
).
).
.
15

Hide quick links: