5. Dress the power cord appropriately. Verify that the power cord does not block the air exhaust and
access to router components, or drape where people could trip on it.
6. Repeat Step
1
through Step
7. Observe the system LED on the router. If an AC power supply is functioning normally, the system LED
lights green steadily.
If the system LED is not lit, the power supply is not functioning normally. Repeat the cabling procedures.

Connect DC Power to a DC-Powered ACX2000 or ACX2100 Router

To connect power to the DC-powered router, you need the following tools:
Phillips (+) screwdriver, number 2
ESD grounding wrist strap
M3 screws and flat washers
DC power source cables, minimum 14 AWG or as required by local code (not provided)
Ring lugs, Molex 190700067 or equivalent (not provided)
The DC power supply has four terminals on the front panel, covered by a clear plastic cover.
Table 1: ACX Series DC Power System Input Voltage
Nominal Voltage
+24
–48
–60
1. Attach an electrostatic discharge (ESD) grounding strap to your bare wrist, and connect the strap to
one of the ESD points on the chassis. For more information about ESD, see the
Universal Access Routers Hardware
2. Switch off the dedicated customer site circuit breakers. Ensure that the voltage across the DC power
source cable leads is 0 V and that there is no chance that the cable leads might become active during
installation.
All manuals and user guides at all-guides.com
5
for the remaining power supplies.
Specification
Operating range: +18 to +30 VDC
Operating range: –39 to –56 VDC
Operating range: –39 to –72 VDC