Output Algorithms; Table 10-13 Set-Up Group - Output - Honeywell UDC2500 Product Manual

Honeywell universal digital controller product manual
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

10.7.5

Output Algorithms

Table 10-13 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Output.
Parameter
Description
Hex
Output
00A0
Algorithm
Relay Cycle
00BE
Time
Increments
Motor Time for
004B
Three Position
Step
Current Range
0099
for Current
Duplex
Current Output
00EA 235
Range
4/07
Modbus Read, Write and Override Parameters plus Exception Codes
Table 10-13 Set-up Group – Output
Register
Data
Address
Type
Decimal
160
INT
190
INT
075
INT
153
INT
INT
UDC2500 Universal Digital Controller Product Manual
Access
Data Range or
Enumerated Selection
R/W
0 = Time Simplex
1 = Not Used
2 = Current Simplex
3 = Three Position Step or
Position Proportioning
4 = Time Duplex
5 = Current Duplex
6 = Current/Time Duplex
7 = Time/Current Duplex
R/W
0 = 1 second increments
1 = 1/3 second increments
R/W
5 to 1800 seconds
0 = Full (100%)
R/W
1 = Split (50%)
0 = 4-20 mA
R/W
1 = 0-20 mA
203