Step 10- Operate Ecm Interface Board; Heating; Cfm Adjust; Dehumidification Mode - Carrier PTV Installation, Start-Up And Service Instructions Manual

Two-stage water source heat pumps with puron refrigerant (r-410a)
Table of Contents

Advertisement

Step
10 --
Operate
ECM
Interface
Board
The ECM fan is controlled
by an interface board that converts
thermostat
inputs and field selectable
cfm settings to signals
used by the ECM (electronically
colmnutated
motor) control-
ler. See Fig. 35.
NOTE: Power must be offto
the unit for at least three seconds
before the ECM will recognize a speed change. The motor will
recognize
a change in the CFM Adjust
or Dehumidification
mode settings while the unit is powered.
There are four different airflow settings from lowest airflow
rate (speed tap 1) to the highest
airflow rate (speed tap 4).
Tables 9-13 indicate settings for the ECM interface
board, fol-
lowed by detailed reformation
for each setting.
When
the disconnect
switch
is closed,
high voltage
is
present in some areas of the electrical panel. Exercise
cau-
tion when working with energized equipment.
COOLING--The
cooling
setting
determines
the cooling
(normal) cfm for all units with ECM motor. Cooling (normal)
setting is used when the unit is not in Dehumidification
mode.
Tap 1 is the lowest cfm setting, while tap 4 is the highest cfm
setting. To avoid air coil freeze-up,
tap 1 may not be used if the
Dehumidification
mode is selected. See Table 9.
Table 9 -- Cooling Settings
TAP SETTING
1
2
3
4
DIP SWITCH
SWl
ON
ON
OFF
OFF
SW2
ON
OFF
ON
OFF
HEATING
-- The heating setting determines
the heating cfm
for 50PTH,PTV, PTD units. Tap 1 is the lowest cfm setting,
while tap 4 is the highest cfm setting. See Table 10.
Table 10-
Heating Settings
TAP SETTING
1
2
3
4
SW3
ON
ON
OFF
OFF
DIP SWITCH
SW4
ON
OFF
ON
OFF
CFM ADJUST
-- The CFM Adjust setting allows four selec-
tions. The NORM setting is the factory default position. The +
or- settings adjust the airflow by ±15%. The + or- settings are
used to "fine rune" airflow adjusUnents.
The TEST setting runs
the ECM at 70% torque,
which causes the motor to operate
like a standard PSC motor, and disables the cfm counter. See
Table 11.
Table 11 -- CFM Adjust Settings
TAP SETTING
TEST
+
NORM
SW7
ON
ON
OFF
OFF
DIP SWITCH
SW8
ON
OFF
ON
OFF
DEHUMIDIFICATION
MODE
--The
dehumidification
mode setting provides field selection of humidity control.
When operating in the normal mode, the cooling airflow set-
tings are determined by the cooling tap setting in Table 12.
Table 12 -- Dehumidificaton
Mode Settings
TAP SETTING
NORM
Dehumid
DIP SWITCH
SW9
ON
OFF
When dehumidification
is enabled,
there is a reduction
in
airflow in cooling to increase the moisture removal of the heat
pump.
The Dehumidification
mode can be enabled
in two
ways:
1. Constant Dehumidification
mode: When the Dehumidifi-
cation mode is selected via DIP switch, the ECM will
operate
with a multiplier
applied
to the cooling
CFM
settings
(approximately
20 to 25% lower airflow). Any
time the unit is running in the Cooling mode, it will oper-
ate at the lower airflow to improve
latent capacity. The
"DEHUM"
LED will be illuminated
at all thnes. Heating
airflow is not affected.
2.
NOTE:
Do not select Dehumidification
mode if cooling
setting is tap 1.
Automatic
(humidistat-controlled)
Dehumidification
mode:
When
the Dehumidification
mode
is selected
via DIP switch AND a humidistat
is connected
to termi-
nal DH, the cooling airflow will only be reduced
when
the humidistat
senses that additional
dehumidification
is
required.
The DH terminal
is reverse
logic. Therefore,
a
humidistat
(not
dehumidistat)
is
required.
The
"DEHUM"
LED will be illuminated
only when the humi-
distat
is calling
for Dehumidification
mode.
Heating
airflow is not affected.
NOTE:
Do not select Dehumidification
mode if cooling
setting is tap 1.
I_'ISPADE
CONNECTIONS
TO COMPLETE
C OR_
DELUXE
D BOARD
THERMOSTAT
CONNECTIONS
\
\
DEHUMIDIFICATIQN
LED
=<
M
r_ u_u_r__ocou_u_ r_
P_
f
/
J
FAN SPEED
SELECTION
DIP SWITCH
THERMOSTAT
INPUT LEDS
CFM COUNTER
1 FLASH PER 100 CFM
ECM MOTOR
LOW VOLTAGE
CONNECTOR
Fig. 35 -- ECM Interface Board Physical Layout
3O