Split-system heat pump with r-410a refrigerant 1-1/2 to 5 tons

Advertisement

Quick Links

PH14*B, PH15NB, PH16NC
SPLIT-SYSTEM HEAT PUMP
WITH R-410A REFRIGERANT
1-1/2 TO 5 TONS
NOTE: Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or
use can cause explosion, fire, electrical shock, or other conditions which
may cause death, personal injury, or property damage. Consult a
qualified installer, service agency, or your distributor or branch for
information or assistance. The qualified installer or agency must use
factory–authorized kits or accessories when modifying this product.
Refer to the individual instructions packaged with the kits or accessories
when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and
work gloves. Use quenching cloth for brazing operations. Have fire
extinguisher available. Read these instructions thoroughly and follow all
warnings or cautions included in literature and attached to the unit.
Consult local building codes and current editions of the National
Electrical Code (NEC) NFPA 70. In Canada, refer to current editions of
the Canadian electrical code CSA 22.1.
Recognize safety information. This is the safety–alert symbol
you see this symbol on the unit and in instructions or manuals, be alert to
the potential for personal injury.
Understand these signal words; DANGER, WARNING, and
CAUTION. These words are used with the safety–alert symbol.
DANGER identifies the most serious hazards which will result in severe
personal injury or death.
WARNING signifies hazards which could
result in personal injury or death. CAUTION is used to identify unsafe
practices which may result in minor personal injury or product and
property damage. NOTE is used to highlight suggestions which will
result in enhanced installation, reliability, or operation.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical
disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and tag switch
with a suitable warning label.
WARNING
!
EXPLOSION HAZARD
Failure to follow this warning could result in
death, serious personal injury, and/or property
damage.
Never use air or gases containing oxygen for
leak
compressors. Pressurized mixtures of air or
gases containing oxygen can lead to an
explosion.
Installation Instructions
testing
or
operating
INSTALLATION RECOMMENDATIONS
NOTE: In some cases noise in the living area has been traced to gas
pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where unit
operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate for unit
capacity.
3. Run refrigerant tubes as directly as possible by avoiding
unnecessary turns and bends.
4. Leave some slack between structure and unit to absorb vibration.
5. When passing refrigerant tubes through the wall, seal opening with
RTV or other pliable silicon–based caulk (see
6. Avoid direct tubing contact with water pipes, duct work, floor
joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with a rigid
wire or strap which comes in direct contact with tubing (see
8. Ensure that tubing insulation is pliable and completely surrounds
. When
vapor tube.
9. When necessary, use hanger straps which are 1 in. wide and
conform to shape of tubing insulation (see
10. Isolate hanger straps from insulation by using metal sleeves bent to
conform to shape of insulation.
When outdoor unit is connected to factory–approved indoor unit,
outdoor unit contains system refrigerant charge for operation with AHRI
rated indoor unit when connected by 15 ft. (4.57 m) of field–supplied or
factory accessory tubing. For proper unit operation, check refrigerant
charge using charging information located on control box cover and/or
in the Check Charge section of this instruction.
IMPORTANT: Maximum liquid–line size is 3/8–in. OD for all
refrigerant
residential applications including long line.
IMPORTANT: Always install the factory–supplied liquid–line filter
drier. Obtain replacement filter driers from your distributor or branch.
OUTDOOR WALL
INDOOR WALL
CAULK
INSULATION
THROUGH THE WALL
HANGER STRAP
(AROUND SUCTION
INSULATION
TUBE ONLY)
1" (25.4 mm)
MIN
SUSPENSION
Fig. 1 – Connecting Tubing Installation
Fig.
1).
Fig.
1).
Fig.
1).
LIQUID TUBE
SUCTION TUBE
JOIST
SUCTION TUBE
LIQUID TUBE
A07588

Advertisement

Table of Contents
loading

Summary of Contents for Carrier PH14 B Series

  • Page 1 PH14*B, PH15NB, PH16NC SPLIT-SYSTEM HEAT PUMP WITH R-410A REFRIGERANT 1-1/2 TO 5 TONS Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS INSTALLATION RECOMMENDATIONS Improper installation, adjustment, alteration, service, maintenance, or NOTE: In some cases noise in the living area has been traced to gas use can cause explosion, fire, electrical shock, or other conditions which pulsations from improper installation of equipment.
  • Page 2: Installation

    PH14*B, PH15NB, PH16NC: Installation Instructions INSTALLATION IMPORTANT: Effective January 1, 2015, all split system and packaged air conditioners must be installed pursuant to applicable regional efficiency standards issued by the Department of Energy. CAUTION CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs.
  • Page 3: Make Piping Connections

    PH14*B, PH15NB, PH16NC: Installation Instructions Table 1 – Accessory Usage REQUIRED FOR REQUIRED FOR LOW–AMBIENT REQUIRED FOR SEA COAST Accessory COOLING APPLICATIONS LONG LINE APPLICATIONS* APPLICATIONS (Within 2 (Below 55°F / 12.8°C) miles / 3.22 km) Accumulator Standard Standard Standard Ball Bearing Fan Motor Compressor Start Assist Capacitor and Relay...
  • Page 4: Fire Hazard

    PH14*B, PH15NB, PH16NC: Installation Instructions Table 2 – Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.) LIQUID RATED VAPOR UNIT SIZE Connection Tube Connection Tube Diameter Diameter Diameter Diameter 18, 24 30, 36, 42, 48 1–1/8 * Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance data when using different size and length linesets.
  • Page 5: Electrical Shock Hazard

    PH14*B, PH15NB, PH16NC: Installation Instructions Be sure field wiring complies with local and national fire, safety, and CAUTION electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper UNIT DAMAGE HAZARD voltage.
  • Page 6: Compressor Crankcase Heater

    PH14*B, PH15NB, PH16NC: Installation Instructions A00010 Fig. 10 – 3–Phase Monitor Control (Applies to 3–Phase Units Only) Table 3 – 3–Phase Monitor LED Indicators STATUS No call for compressor operation FLASHING Reversed phase A02325 / A97413 Fig. 11 – Generic Wiring Diagrams Normal (See thermostat Installation Instructions for specific unit Connect Control Wiring...
  • Page 7 PH14*B, PH15NB, PH16NC: Installation Instructions Defrost CAUTION The defrost control is a time/temperature control which includes a field selectable time period between defrost cycles (30, 60, 90, or 120 . For UNIT OPERATION AND SAFETY HAZARD non-Quiet Shift 2 boards the time period is selected using quick connects located at the edge of the board.
  • Page 8 PH14*B, PH15NB, PH16NC: Installation Instructions 2. Disconnect outdoor fan motor lead from OF2 on control board for 6. When you hear reversing valve change position, remove units using PSC motors and from ODF terminal on units with ECM screwdriver immediately; otherwise, control will terminate normal motor (see Fig.
  • Page 9 PH14*B, PH15NB, PH16NC: Installation Instructions QUIET SHIFT INTERVAL TIMER OFF T2 C C O O R W SPEEDUP A05378 Fig. 14 – Quiet Shift-2 Control Board Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 10: Check Charge

    PH14*B, PH15NB, PH16NC: Installation Instructions Check Charge Units with Indoor Pistons Units installed with indoor pistons require charging by the superheat Factory charge amount and desired subcooling are shown on unit rating method. plate. Additional subcooling may be required to achieve optimal heating performance based on the installed indoor unit.
  • Page 11 PH14*B, PH15NB, PH16NC: Installation Instructions Table 5 – Additional Subcooling Required for PH14NB Models Subcooling Delta from Rating Plate Value Outdoor Unit Tonnage Indoor Unit | Additional Subcooling Required CAP**1814AL* CAP**2414AL* CAP**3014AL* CAP**3614AL* CAP**4221AL* CAP**4817AL* CAP**6021AL* CAP**2414AL* CAP**2417AL* CAP**3017AL* CAP**3617AL* CAP**4224AL* CAP**4821AL* CAP**6024AL*...
  • Page 12 PH14*B, PH15NB, PH16NC: Installation Instructions Table 7 – Required Liquid Line Temperatures °F REQUIRED SUBCOOLING TEMPERATURE (°F) LIQUID PRESSURE AT SERVICE VALVE (PSIG) Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 13: Final Checks

    PH14*B, PH15NB, PH16NC: Installation Instructions Table 8 – Superheat Charging (Heat Pump Only) EVAPORATOR ENTERING AIR TEMPERATURE (°F WB) OUTDOOR TEMP (°F) – – – – – – – – – – – – – – – – – – –...
  • Page 14 PH14*B, PH15NB, PH16NC: Installation Instructions © 2021 Carrier. All rights reserved. Edition Date: 06/21 Catalog No: IM-PH14-16-07 A Carrier Company Replaces:IM-PH14-16-06 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.