Stopped Or Malfunctioned Ecm Motor - Carrier PTV Installation, Start-Up And Service Instructions Manual

Two-stage water source heat pumps with puron refrigerant (r-410a)
Table of Contents

Advertisement

Stopped
or Malfunctioned
ECM Motor -- Refer
to Fig. 43 to determine
the possible
cause
of a stopped
or mal-
functioned
ECM
motor.
Follow
the instructions
in the boxes.
DOES BLOWER SPIN FREELY? I
YES
NO
CONFIRM _F EITHER BLOWER
WHEEL IS RUBBING AGAINST
HOUSING OR MOTOR SHAFT
IS SPINNING FREELY, REPA1R
OR REPLACE AS NECESSARY.
IS THERE 115V
SUPPUEO TO MOTOR?
T YES
D_SCONNECT 16 P_N
HARNESS FROM
MOTOR. IS THERE 24V
ACROSS PIN12 & PIN'I
AND P_N12 & PIN3
AT THE HARNESS PLUG?
YES
NO
'CHECK 115V SUPPLY,
CONNECTION
FUSES_
SERVICE SWITCH AND
DOOR SWITCH.
NO
I
STHERE24V
ACROSS R &
B/C ON THE
_NTEGRATED
CONTROL?
I YES
DISCONNECT 16PIN
HARNESS FROM
INTEGIRA,TED CONTROL
_STHERE 24V ACROSS
PIN12 & HNt
AND
PIN12 & P_N3
AT THE CONROL?
YES
CHECK HARNESS
CONNECTIONS
AND WIRE.
l
CHECK 24V SUPPLY
l
NO
_
TO #_,_TEGRATEDCONTROL
NO
_
REPLACE
_NTEGRATED
CONTROL.
TURN THERMOSTAT
MANUAL FAN
SWITCH ON {_F AVAL_BLE)
OR JUMPER
BETWEEN R & G ON INTEGRATED CONTROL.
IS THERE VOLTAGE GREA_R
THAN
12V BE'P¢TEEN P_N15 & PIN1?
NO
j[
CHECK CONNECTIONS _D
W_RES
AT INTEGRATED CONTROL
IF OK
REP_CE
INTEGRATED CONTROL
YES
CHECK CONNECTION ON HARNESS ,AND MOTOR,
RECONNECT HARNESS TO MOTOR
;F
C_NECT_ONS
ARE GOOD AND MOTOR STIL
DOES NOT RUN REPLACE MOTOR_
Fig. 43 -- ECM Troubleshooting
Flow Diagram
51

Advertisement

Table of Contents
loading

This manual is also suitable for:

50pthPtd026-072

Table of Contents