Step 10.-Compressor Crankcase Heater; Step 11.-Install Electrical Accessories; Step 12.-Start- -Up - Carrier 25hba Installation Instructions Manual

Base series puron refrigerant heat pumps sizes 018 to 060
Hide thumbs Also See for 25hba:
Table of Contents

Advertisement

CONNECT GROUND AND POWER WIRES
Connect ground wire to ground connection in control box for
safety. Connect power wiring to contactor as shown in Fig. 10.
DISCONNECT
PER N. E. C. AND/OR
LOCAL CODES
FIELD POWER
WIRING
FIELD GROUND
WIRING
Fig. 10 - - Line Connections
CONNECT CONTROL WIRING
Route 24v control wires through control wiring grommet and
connect leads to control wiring. See Thermostat Installation
Instructions for wiring specific unit combinations. (See Fig. 11.)
Use No. 18 AWG color- -coded, insulated (35°C minimum) wire.
If thermostat is located more than 100 ft from unit, as measured
along the control voltage wires, use No. 16 AWG color- -coded
wire to avoid excessive voltage drop.
All wiring must be NEC Class 1 and must be separated from
incoming power leads.
Use furnace transformer, fan coil transformer, or accessory
transformer for control power, 24v/40va minimum.
NOTE: Use of available 24v accessories may exceed the
minimum 40va power requirement. Determine total transformer
loading and increase the transformer capacity or split the load
with an accessory transformer as required.
FINAL WIRING CHECK
IMPORTANT: Check factory wiring and field wire connections
to ensure terminations are secured properly. Check wire routing to
ensure wires are not in contact with tubing, sheet metal, etc.
Step 10.—Compressor Crankcase Heater
When equipped with a crankcase heater, furnish power to heater a
minimum of 24 hr before starting unit. To furnish power to heater
only, set thermostat to OFF and close electrical disconnect to
outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than
80 ft. Refer to the Long Line Guideline- -Residential Split- -System
Air Conditioners and Heat Pumps.
Step 11.—Install Electrical Accessories
Refer to the individual installation instructions packaged with kits
or accessories when installing.
CONTACTOR
GROUND
LUG
A91056
Step 12.—Start- -Up
CAUTION
!
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this caution may result in minor personal injury,
equipment damage or improper operation.
To prevent compressor damage or personal injury,
observe the following:
S Do not overcharge system with refrigerant.
S Do not operate unit in a vacuum or at negative pressure.
S Do not disable low pressure switch in scroll compressor
applications.
S Dome temperatures may be hot.
CAUTION
!
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal
injury.
To prevent personal injury wear safety glasses, protective
clothing, and gloves when handling refrigerant and observe the
following:
S Back seating service valves are not equipped with Schrader
valves. Fully back seat (counter clockwise) valve stem
before removing gage port cap.
S Front seating service valves are equipped with Schrader
valves.
CAUTION
!
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental
damage.
Federal regulations require that you do not vent refrigerant to the
atmosphere. Recover during system repair or final unit disposal.