Step 8 -- Wire Field Power Supply - Carrier PTV Installation, Start-Up And Service Instructions Manual

Two-stage water source heat pumps with puron refrigerant (r-410a)
Table of Contents

Advertisement

Table 2 -- Water Quality Guidelines
I
HX
CLOSED RECIRCULATINGt"
OPEN LOOP AND RECIRCULATING
WELL**
CONDITION
MATERIAL*
Scaling Potential -- Primary Measurement
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated
using the limits below.
Hardness
Method
All
N/A
pH < 7.5 and Ca Hardness, <100 ppm
Index Limits for Probable
Scaling
Situations
(Operation
outside
these limits
is not recommended.)
Scaling indexes should be calculated
at 150 F for direct use and HWG applications,
and at 90 F for indirect HX use. A monitoring
plan should be
implemented.
6.0 - 7.5
Ryznar Stability Index
All
N/A
if >7.5 minimize steel pipe use.
Langelier
Saturation
Index
-0.5 to +0.5
All
N/A
If <-0.5 minimize steel pipe use.
Based upon 150 F HWG and direct well, 85 F indirect well HX.
Iron Fouling
Iron Fe 2+ (Ferrous)
<0.2 ppm (Ferrous)
(Bacterial
Iron Potential)
All
N/A
If Fe2+ (ferrous) >0.2 ppm with pH 6 - 8, 02<5 ppm check for iron bacteria.
Iron Fouling
All
N/A
<0.5 ppm of Oxygen
Above this level deposition will occur.
Corrosion
Preventionll
6 - 8.5
6 - 8.5
pH
All
Monitor/treat
as needed.
Minimize steel pipe below 7 and no open tanks with pH <8.
Hydrogen Sulfide (H2S)
<0.5 ppm
All
N/A
At H2S>0.2 ppm, avoid use of copper and cupronickel
piping or HXs.
Rotten egg smell appears at 0.5 ppm level.
Copper alloy (bronze or brass) cast components
are okay to <0.5 ppm.
Ammonia
ion as Hydroxide,
<0.5 ppm
Chloride, Nitrate and Sulfate
All
N/A
Compounds
Maximum Chloride Levels
Copper
Cupronickel
304 SS
316 SS
Titanium
N/A
N/A
N/A
N/A
N/A
Maximum
allowable at maximum water temperature.
5O F (10 C)
75 F (24 C)
100 F (38 C)
<20 ppm
NR
NR
<150 ppm
NR
NR
<400 ppm
<250 ppm
<150 ppm
<1000 ppm
<550 ppm
<375 ppm
>1000 ppm
>550 ppm
>375 ppm
Erosion and Clogging
Particulate
Size and Erosion
<10 ppm of particles
and a
<10 ppm (<1 ppm "sandfree"
for reinjection)
of particles
and a maximum velocity
All
maximum velocity of 6 fps.
of 6 fps. Filtered for maximum 800 micron size. Any particulate
that is not
Filtered for maximum
removed can potentially clog components.
800 micron size.
Brackish
Use cupronickel
heat exchanger when concentrations
of calcium or sodium chic-
All
N/A
ride are greater than 125 ppm are present.
(Seawater is approximately
25,000
ppm.)
LEGEND
HWG
--
Hot Water Generator
HX
--
Heat Exchanger
N/A
--
Design Limits Not Applicable
Considering
Recirculating
Potable Water
NR
--
Application
Not Recommended
SS
--
Stainless Steel
*Heat
exchanger
materials
considered
are copper,
cupronickel,
304 SS
(stainless steel), 316 SS, titanium.
tCIosed
recirculating
system
is identified
by a closed
pressurized
piping
system.
**Recirculating
open
wells
should
observe
the open
recirculating
design
considerations.
ttlf
the concentration
of these corrosives
exceeds
the maximum
allowable
level, then the potential for serious corrosion
problems exists.
Sulfides
in the water quickly oxidize when exposed
to air, requiring that no
agitation
occur as the sample
is taken.
Unless tested
immediately
at the
site, the sample will require stabilization
with a few drops of one Molar zinc
acetate
solution,
allowing
accurate
sulfide determination
up to 24 hours
after sampling.
A low pH and high alkalinity cause system problems,
even
when both values are within ranges shown. The term pH refers to the acid-
ity, basicity, or neutrality of the water supply. Below 7.0, the water is consid-
ered to be acidic. Above 7.0, water is considered
to be basic. Neutral water
contains a pH of 7.0.
To convert
ppm to grains
per gallon,
divide
by 17. Hardness
in mg/I is
equivalent
to ppm.
Table 3 -- Metal Hose Minimum Bend Radii
HOSE DIAMETER
(in.)
MINIMUM BEND RADII (in.)
1/2
21/2
3/4
4
1
51/2
Swivel
Brass \
Brass
....
_.,
....................................................................
Rib Crimped_tting
\
....
Fit}ing
I
(2 ft LeLgth Standard)
4
MPT
Fig. 14 -- Supply/Return
Hose Kit
Step 8 E Wire Field Power Supply
To avoid possible
injury or death due to electrical
shock,
open the power supply disconnect
switch and secure it in
an open position during installation.
Use only copper
conductors
for field-installed
electrical
wiring.
Unit terminals
are not designed
to accept
other
types of conductors.
All field-installed
wiring, including
the electrical
ground,
MUST
comply
with the National
Electrical
Code (NEC)
as
well as applicable local codes. In addition, all field wiring must
12