Carrier PTV Installation, Start-Up And Service Instructions Manual page 60

Two-stage water source heat pumps with puron refrigerant (r-410a)
Table of Contents

Advertisement

APPENDIX
A E WSHP SCREEN
OPEN CONFIGURATION
(cont)
SCREEN
NAME
Configuration
4.
Alarm
Configuration
Configuration
4.
Linkage
POINT NAME
SPT Occupied Alarm
Hysteresis
SPT Alarm Delay
SPT Unoccupied
Low
Alarm Temperature
SPT Unoccupied
High
Alarm Temperature
SAT Low SAT
Alarm Limit
SAT High SAT
Alarm Limit
Condensate
Overflow
Alarm Delay
Space Humidity Occupied
High Alarm Limit
Space Humidity Alarm
Delay
Space Humidity Unoccu-
pied High Alarm Limit
IAQNentilation
Occupied
High Alarm Limit
IAQ/Ventilation
Alarm Delay
Rnet Sensor SPT Alarm
Rnet Sensor SAT Alarm
Rnet Sensor Compressor
Lockout Alarm
Rnet Sensor Condenser
Water Temperature
Alarm
Rnet Sensor Condensate
Overflow Alarm
Rnet Sensor Dirty
Filter Alarm
Rnet Sensor Space
High Humidity Alarm
Loop Control Network
Number
Loop Control Network
Address
Number of Linked Heat
Pumps
LEGEND
BAS
--
Building Automation
System
DCV
--
Demand Controlled Ventilation
IAQ
--
Indoor Air Quality
OAT
-- Outdoor Air Temperature
RH
--
Relative Humidity
SAT
--
Supply Air Temperature
SPT
--
Space Temperature
TPI
-- Third Party Integration
PASSWORD
LEVEL
EDITABLE
RANGE
DEFAULT
X
2-20
° F
5 ° F
Admin Password
level access only
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
0 - 30 min per degree
10 min
35- 90 ° F
45 ° F
45-
100 ° F
95 ° F
15- 90 ° F
45 ° F
90- 175 ° F
120 ° F
5 - 600 sec
10 sec
45%- 100%
100%
0- 30 min per % RH
5 min
45%- 100%
100%
0 - 9999 ppm
1100 ppm
0.1 - 1.0 min per ppm
0.25 min
Ignore/Display
Ignore
Ignore/Display
Ignore
Ignore/Display
Display
Ignore/Display
Display
Ignore/Display
Display
Ignore/Display
Display
Ignore/Display
Ignore
NOTES
Defines the hysteresis applied above
the cooling and below the heating set
points before an alarm condition will
occur
Used to calculate the delay time before
an alarm is generated after the alarm
condition occurs
Defines the fixed unoccupied
ow SPT alarm limit
Defines the fixed unoccupied
high SPT alarm limit
Defines the fixed minimum
SAT alarm limit
Defines the fixed maximum
SAT alarm limit
Defines the delay time before an alarm
is generated
after the alarm condition
OCCUrs
Defines the fixed occupied
high space RH alarm limit
Used to calculate the delay time before
an alarm is generated after the alarm
condition occurs
Defines the fixed unnoccupied
high space RH alarm limit
Defines the fixed occupied high
space IAQNentilation
alarm limit
Used to calculate the delay time before
an alarm is generated after the alarm
condition occurs
Determines
if the SPT alarm is
displayed on the local Rnet sensor
Determines
if the SAT alarm is
displayed on the local Rnet sensor
Determines
if the Compressor
Lockout
alarm is displayed on the local Rnet
sensor
Determines
if the Condenser
Water
Temperature
alarm is displayed
on the
local Rnet sensor
Determines
if the Condensate
Overflow alarm is displayed
on the
local Rnet sensor
Determines
if the Dirty Filter alarm is
displayed on the local Rnet sensor
Determines
if the High Space
RH alarm is displayed on the
local Rnet sensor
See TPI
See TPI
See TPI
d0