Ground-Loop Applications; Installation Of Supply And Return Hose - Carrier PTV Installation, Start-Up And Service Instructions Manual

Two-stage water source heat pumps with puron refrigerant (r-410a)
Table of Contents

Advertisement

Water
Flow
Control
Regulator
Valve
(field-installed
(field-installed
accessory)
accessory)
Pressure
Tank
Water Out
Water In
Pump
Boiler
Drains
(field-installed)
Shut-Off
Valve (field-installed
accessory)
Strainer (field-installed
accessory)
(16 to 20 mesh recommended
for
filter sediment)
Fig. 13 -- Typical Ground-Water Piping Installation
Water Supply and Quantity
--
Check
water
supply.
Water
supply should be plentiful and of good quality. See Table 2 for
water quality guidelines.
IMPORTANT:
Failure to comply with the above required
water
quality
and quantity
limitations
and the closed-
system application
design requirements
may cause damage
to the tube-in-tube
heat exchanger.
This damage is not the
responsibility
of the manufacturer.
In all applications,
the quality
of the water
circulated
through the heat exchanger
must fall within the ranges listed in
the Water Quality Guidelines
table. Consult a local water treat-
ment firm, independent
testing facility, or local water authority
for specific recolranendations
to maintain water quality within
the published
lhnits.
GROUND-LOOP
APPLICATIONS
-- Temperatures
between
25 and 110 F and a cooling capacity of 2.25 to 3 gpm of flow
per ton is recolranended.
In addition
to complying
with any
applicable codes, consider the following
for system piping:
Limit piping materials
to only polyethylene
fusion in the
buried sections of the loop.
Do not use galvanized
or steel fittings at any time due to
corrosion.
Avoid all plastic to metal threaded
fittings due to the poten-
tial to leak. Use a flange fitted substitute.
Do not overtighten
connections.
Route piping to avoid service access areas to unit.
Use pressure-temperature
(P/T) plugs to measure
flow of
pressure drop.
INSTALLATION
OF
SUPPLY
AND
RETURN
HOSE
KIT -- Follow these piping guidelines.
1. Install a dram valve at the base of each supply and return
riser to facilitate system flushing.
2. Install shutof_balancing
valves and unions at each unit to
permit unit removal for servicing.
3. Place
strainers
at the inlet of each system
circulating
pump.
4. Select the proper hose length to allow slack between con-
nection points. Hoses may vary in length by +2% to -4%
under pressure.
5.
Refer to Table 3. Do not exceed the minhnum
bend radius
for the hose selected. Exceeding
the minhnum
bend radi-
us may cause the hose to collapse,
which reduces
water
flow rate. Install an angle adapter
to avoid sharp bends
in the hose when the radius
falls below
the required
minimum.
NOTE: Piping must comply with all applicable codes.
Insulation is not required on loop water piping except where
the piping runs through unheated
areas or outside the building
or when the loop water temperature
is below the minimum
ex-
pected dew point of the pipe ambient. Insulation
is required if
loop water temperature
drops below the dew point.
Do not bend or kink supply lines or hoses.
Pipe joint compound
is not necessary when Teflon threaded
tape is pre-applied
to hose assemblies
or when
flared-end
connections
are used. If pipe joint compound
is preferred,
use
compound
only m small amounts on the male pipe threads of
the fitting adapters.
Prevent
sealant from reaching
the flared
surfaces of the
:joint.
NOTE: When anti-freeze
is used m the loop, assure that it is
compatible
with Teflon tape or pipe joint compound
employed.
Maximum
allowable torque for brass fittings is 30 ft-Ib. Ifa
torque wrench
is not available,
tighten
finger-tight
plus one
quarter turn. Tighten steel fittings as necessary.
Optional
pressure-rated
hose assemblies
designed
specifi-
cally for use with Carrier units are available.
Similar hoses can
be obtained
from alternate
suppliers.
Supply and return hoses
are fitted with swivel-joint
fittings at one end to prevent kink-
ing during installation.
Backup wrench is required when tightening water connec-
tions to prevent water line damage.
Refer to Fig. 14 for an illustration of a supply/return hose
kit. Male adapters secure hose assemblies to the unit and risers.
Install hose assemblies properly and check them regularly to
avoid system failure and reduced service life.
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

50pthPtd026-072

Table of Contents