APPENDIX
A E WSHP OPEN
SCREEN
CONFIGURATION
(cont)
SCREEN NAME
Configuration
Set Points
Configuration
$
Schedule
$
Weekly Schedule
Configuration
Schedule
Exception
Schedules
1 - 12
POINT NAME
Occupied
Heating
Occupied Cooling
Unoccupied
Heating
Unoccupied
Cooling
Effective Heating
Set Point
Effective Cooling
Set Point
Optimal Start
Occupied RH
Set Point
Unoccupied
RH
Set Point
DCV CTRL Start
Set Point
DCV Max CTRL
Set Point
Start Time
End Time
Mon
Tue
Wed
Thur
Fri
Sat
Sun
Start Month
Start Day
Start Time
End Month
End Day
End Time
PASSWORD
LEVEL
User/Admin
Password
level
access
User/Admin
Password level
access
User/Admin
Password level
access
EDITABLE
X
X
X
X
X
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
RANGE
DEFAULT
40 - 90 o F
72 o F
55 - 99 o F
76 o F
40 - 90 o F
55 o F
55-99°
F
90° F
0-10°F
0-10°F
0 - 100%
0 - 100%
0 - 9999
ppm
500
ppm
0 - 9999
ppm
1050
ppm
00:00 - 23:59
00:00 - 24:00
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
0-12
0- 31
00:00 - 23:59
0-12
O- 31
00:00 - 24:00
NOTES
Defines the Occupied
Heating Set Point
Defines the Occupied
Cooling Set Point
Defines the Unoccupied
Heating Set Point
Defines the Unoccupied
Cooling Set Point
Takes into effect bias (maximum
allowable set point deviation)
Takes into effect bias (maximum
allowable set point deviation)
Uses historical
data to calculate
ramp up time so as to be at set point
at occupied/unoccupied
time
Defines the control set point used
during occupied periods (Viewable
65%
only if Humidity Sensor = Installed/
Determines
when to start
Dehumidification
when occupied)
Defines the control set point used
during unoccupied
periods
90%
(Viewable only if Humidity
Sensor =
Installed/Determines
when to start
Dehumidification
when unoccupied)
Defines the control set point used to
start increasing
ventilation during
occupied periods (Viewable only if
Ventilation DMP Type = DCV)
Defines the control set point
used to define where the ventilation
will reach its maximum limit during
occupied periods (Viewable only if
Ventilation DMP Type = DCV/Used
to determine
DCV ending control
point)
06:00
Defines the start time for an
occupied period
18:00
Defines the ending time of an
occupied period
Determines
if this day is included
Yes
in this schedule
Determines
if this day is included
Yes
in this schedule
Determines
if this day is included
Yes
in this schedule
Determines
if this day is included
Yes
in this schedule
Yes
Determines
if this day is included
in this schedule
No
Determines
if this day is included
in this schedule
No
Determines
if this day is included
in this schedule
Defines the start month of this
0
holiday schedule
Defines the start day of this holiday
0
schedule
Determines
the start time for this
0:00
schedule
Defines the month to end this
0
holiday schedule
0
Defines the day to end this holiday
schedule
0:00
Determines
the time to end this
schedule
LEGEND
BAS
--
Building Automation
System
DCV
--
Demand Controlled Ventilation
IAQ
--
Indoor Air Quality
OAT
-- Outdoor Air Temperature
RH
--
Relative Humidity
SAT
--
Supply Air Temperature
SPT
--
Space Temperature
TPI
-- Third Party Integration