Carrier PTV Installation, Start-Up And Service Instructions Manual page 54

Two-stage water source heat pumps with puron refrigerant (r-410a)
Table of Contents

Advertisement

Table 32 -- WSHP Troubleshooting
(cont)
FAULT
HEATING
High Head Pressure
X
Low Suction Pressure
Low Discharge Air
Temperature
in Heating
High Humidity
Low Refrigerant
Suction
Pressure
High Refrigerant
Superheat
High Refrigerant
Subcooling
x
x
x
x
COOLING
X
X
x
x
x
x
x
x
x
x
x
x
x
x
x
POSSIBLE
CAUSE
Reduced or no airflow in heating
Reduced or no water flow in
cooling
Inlet water too hot
Air temperature
out of range in
heating
Scaling in water heat exchanger
Unit overcharged
Noncondensables
in system
Restricted
metering device
Reduced water flow in heating
Water temperature
out of range
Reduced airflow in cooling
Air temperature
out of range
Insufficient
charge
Too high airflow
Poor performance
Too high airflow
Unit oversized
X
Normal operation
X
Reduced water flow
X
Water temperature
out of range
X
Scaling in water to refrigerant
heat exchanger
X
Reduced airflow
Return air temperature
below
minimum
SOLUTION
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
External static too high. Check blower performance
per Tables 9-13.
Check pump operation or valve operation/setting.
Check water flow adjust to proper flow rate. See Tables 19 and 24.
Check load, loop sizing, loop backfill, ground moisture.
Bring return-air temperature
within design parameters.
Perform condenser
cleaning.
Check superheat
and subcooling.
Reweigh in charge.
Remove refrigerant, evacuate system and charge unit.
Check superheat
and subcooling
per Tables 20-23. Replace.
Check pump operation or water valve operation/setting.
Plugged strainer or filter. Clean or replace.
Check water flow adjust to proper flow rate.
Bring water temperature
within design parameters.
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
External static too high. Check blower performance
per Tables 9-13.
Too much cold vent air. Bring entering
air temperature
within design
parameters.
Check for refrigerant
leaks.
Check blower performance
per Tables 9-13.
See "Insufficient
Capacity."
Check blower performance
per Tables 9-13
Recheck loads and sizing check sensible cooling load and heat pump
capacity.
Check/compare
with unit Installation
Manual for typical operating temper-
atures and pressures chart.
Check pump operation.
Check strainer or filter.
Improper flow regulator.
Bring water temperature
within proper range.
Conduct water quality analysis.
Check for dirty air filter.
Check for dirty air coil.
Check fan motor operation.
External static pressure exceeds fan operating parameters.
Space temperature
too cold.
Excessive fresh air.
Check for leaking ductwork.
X
Locate and repair leak.
X
Locate bulb on suction line between
reversing valve and compressor.
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Supply air bypassing to return air
stream (zone systems).
Insufficient
refrigerant charge
Improperly
located TXV sensing
bulb
Failed or restricted
metering
device
Insufficient
refrigerant charge
Improperly
located TXV sensing
bulb
Failed or restricted
metering
device
Excessive
refrigerant charge
Failed or restricted
metering
device
Normal operation
Insufficient
refrigerant charge
Failed or restricted
metering
device
Failed or restricted
metering
device
X
X
TXV and/or Low Pressure
X
Tubing
Frosting
X
X
Equalizer
Line Condensing
or Frosting
Failed TXV power head, capillary or sensing bulb.
Plugged TXV strainer.
Locate and repair leak.
Locate bulb on suction line between
reversing valve and compressor.
Failed TXV power head, capillary or sensing bulb.
Plugged TXV strainer.
Remove refrigerant as needed.
Failed TXV power head, capillary or sensing bulb.
Plugged TXV strainer.
May occur when entering water temperature
is close to minimum.
Locate and repair leak.
Failed TXV power head, capillary or sensing bulb.
Plugged TXV strainer.
Failed TXV power head, capillary or sensing bulb.
Plugged TXV strainer.
LEGEND
LED
--
Light-Emitting
Diode
RV
--
Reversing
Valve
TXV
--
Thermostatic
Expansion
Valve
54