WSHP Open Test Mode -- To
enter WSHP Open test
mode, navigate from the BACview 6 home screen to the config-
uration screen. Choose the service screen and enable unit test.
The controller will then test the following:
FAN TEST -- Tests all fan speeds, sequences
fan from low to
high, and operates each speed for one minute. Resets to disable
on completion.
COMPRESSOR
TEST--Tests
compressor
cooling
and
heating
operation.
Sequences
cooling
stage
1 then cooling
stage 2 followed
by heating
stage 2 then reduces
capacity to
heating stage 1. Operates for 1 minute per step.
DEHUMIDIFICATION
TEST
--
Tests dehumidification
mode. Operates for 2 minutes.
AUXILIARY
HEATING
TEST -- Tests
auxiliary
heat.
Sequences
fan on and enables heating coil for 1 minute.
H20
ECONOMIZER
TEST
--
Tests
entering/returning
water loop economizer
operation.
Sequences
fan and opens
economizer
water valve for one minute.
OPEN VENT DAMPER
100% TEST -- Tests
outside
air
(OA) damper operation.
PREPOSITION
OA DAMPER
-- Prepositions
OA damper
actuator to set proper preload.
NOTE: The auxiliary heating test, H20 economizer
test, open
vent damper
100% test, and preposition
OA damper features
will not be visible on the screen unless configured.
Once tests are complete,
set unit test back to disable. Unit will
automatically
reset to disable after 1 hour.
Retry Mode
--
In Retry mode, the status LED will start to
flash slowly to signal that the control is trying to recover from
an input fault. The control will stage off the outputs and try to
again satisfy the thermostat
used to terminal Y. Once the ther-
mostat input calls are satisfied, the control will continue normal
operation.
NOTE:
If 3 consecutive
faults occur without
satisfying
the
thermostat
input call to terminal
Y, the control will go into
lockout mode. The last fault causing the lockout is stored in
memory and can be viewed by entering Test mode.
Aquazone
TM
Deluxe
D Control
LED
Indica-
tors
--
There are 3 LED indicators
on the Deluxe D control:
STATUS LED-
Status LED indicates
the current status or
mode of the D control. The Status LED light is green.
TEST LED-
Test LED will be activated
any time the D
control is in test mode. The Test LED light is yellow.
FAULT LED -- Fault LED light is red. The fault LED will
always flash a code representing
the last fault in memory.
If
there is no fault in memory, the fault LED will flash code 1 and
appear as one fast flash alternating
with a 10-second
pause.
See Table 29.
Table 29 -- Ac uazone Deluxe D Control Current LED Status and Alarm Relay Operations
STATUS LED
TEST LED
DESCRIPTION
(Green)
(Yellow)
FAULT LED (Red)
ALARM RELAY
Normal Mode
On
Off
Flash Last Fault Code in Memory
Open
Cycle (closed 5 sec,
Normal
Mode with PM
On
Off
Flashing Code 8
open 25 sec .... )
Deluxe D Control
Off
Off
Off
Open
is non-functional
Test Mode
--
On
Flash Last Fault Code in Memory
Cycling Appropriate Code
Night Setback
Flashing Code 2
--
Flash Last Fault Code in Memory
--
ESD
Flashing Code 3
--
Flash Last Fault Code in Memory
--
Invalid T-stat Inputs
Flashing Code 4
--
Flash Last Fault Code in Memory
--
No Fault in Memory
On
Off
Flashing Code 1
Open
HP Fault
Slow Flash
Off
Flashing Code 2
Open
LP Fault
Slow Flash
Off
Flashing Code 3
Open
FP1 Fault
Slow Flash
Off
Flashing Code 4
Open
FP2 Fault
Slow Flash
Off
Flashing Code 5
Open
CO Fault
Slow Flash
Off
Flashing Code 6
Open
Over/Under
Voltage
Slow Flash
Off
Flashing Code 7
Open (closed after 15 minutes)
HP Lockout
Fast Flash
Off
Flashing Code 2
Closed
LP Lockout
Fast Flash
Off
Flashing Code 3
Closed
FP1 Lockout
Fast Flash
Off
Flashing Code 4
Closed
FP2 Lockout
Fast Flash
Off
Flashing Code 5
Closed
CO Lockout
Fast Flash
Off
Flashing Code 6
Closed
LEGEND
CO
--
Condensate Overflow
HP
--
High Pressure
ESD --
Emergency Shutdown
LP
--
Low Pressure
FP
--
Freeze Protection
PM
--
Performance Monitor
NOTES:
1, If there is no fault in memory, the Fault LED will flash code 1,
2, Codes will be displayed with a 10-second Fault LED pause,
3, Slow flash is 1 flash every 2 seconds,
4, Fast flash is 2 flashes every 1 second,
5, EXAMPLE: "Flashing Code 2" is represented
by 2 fast flashes
followed by a 10-second pause, This sequence will repeat con-
tinually until the fault is cleared,