2.8.5
Conditions power supply
Operating conditions
Power supply voltage
Circuit breaker
Frequency
Enclosure rating
Tab. 8 Power supply
2.8.6
Conditions for hydraulic system and water quality
Operating conditions
Operating pressure (above
atmospheric)
Permissible site test pressure
Safety temperature limitation by
TR temperature control
Safety temperature limitation by
manual reset high limit (STB)
Water quality
Tab. 9 System configuration and water quality
Logano G115 WS US/CA - Technical specifications are subject to change without prior notice.
Notes – Requirement in greater detail
120 V
Observe the voltage range of the burner and controls used. The outer casing/boiler must
AC nominal
be grounded for safety reasons and in order to function correctly.
10 A
60 Hz
−
IP 40 (protected against contact by entry of foreign objects > 0.04 inches Ø
(> 1 mm Ø ), no water proofing)
Notes – Requirement in greater detail
15 – 58 psi
Maximum 30 psi with the supplied safety valve.
45 – 75 psi
122 – 194 °F
212 – 248 °F
On some controls adjustable on site from 212 to 248 °F.
−
The heating system may only be filled and topped up with water of domestic water quality.
We recommend a pH value of 8.2 – 9.5.
Product description
2
11