Mantel And Wall Projections - Heat & Glo MEZZO-1000-AU Installation Manual

Hide thumbs Also See for MEZZO-1000-AU:
Table of Contents

Advertisement

B. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances to combustibles as specified. Framing closer than the
minimums listed must be constructed entirely of noncom-
bustible materials (i.e., steel studs, concrete board, etc.)
For non-combustible fireplace finish material (marble,
Note:
stone, etc) specifications refer to Section 10.A.
Combustible Mantels
M A X .
9 in. (229 mm)
6 in. (152 mm) 3
in. (76 mm)
1 in. (25 mm)
MEASUREMENT FROM
TOP EDGE OPENING
Measurement from top edge opening to
bottom of appliance = 24-1/2 in. (622 mm)
4 Figure 10.7 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles - MEZZO-1000-AU
MEZZO-1300-AU, MEZZO-1300ST-AU
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. D • 3/15
48
TO CEILING
12 in. (305 mm)
M A X .
6 in. (152 mm)
3 in. (76 mm)
Measurement from top edge opening to
bottom of appliance = 24-1/2 in. (622 mm)
4 Figure 10.8 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles - MEZZO-1600-AU
TO CEILING
9 in. (229 mm)
MEASUREMENT FROM
TOP EDGE OPENING