Heat & Glo MEZZO-1000-AU Installation Manual page 57

Hide thumbs Also See for MEZZO-1000-AU:
Table of Contents

Advertisement

A. V e n t C om p on e n t s D i a gr a m s (
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).
used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick.
the existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-
HSM-B will be required.
15-1/8 in.
(384
mm)
DVP-TRAP2
Horizontal Termination Cap
Figure 12.2 DVP Vent Components
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. D • 3/15
continued )
___ 8 in.
(203 mm)
12 in. _
(305 mm)
1 in.
(25 mm)
14 in.
(356 mm)
The heat shield is designed to be
If wall thickness is less than 4 in. (102 mm)
Heat
Shield
Term Cap
Max
Effective
Length
DVP-TRAP2
7-1/4 in.
(184 mm)
3/8 in. (10 mm)
1 in. (25 mm)
7-3/4 to 10-3/8 in.
(197 to 264 mm)
DVP-FBHT
FireBrickTermination Cap
Minimum
Effective Length
3-1/8 in.
Trap1
79 mm
5-3/8 in.
Trap2
137 mm
Maximum
Effective Length
4-5/8 in.
117 mm
9-3/8 in.
238 mm
55