MULTIQUIP TLG8SSK4F Operation And Parts Manual page 35

Portable generator
Table of Contents

Advertisement

Cleaning the Fuel Filter
Every 100 hours: Clean fuel filter every 100 hours of
operation or once a month to remove dust or water.
1. Place fuel cock lever (Figure 38) in the close position.
2. Disconnect fuel lines from fuel filter.
Figure 38. Fuel Cock Lever (OFF)
Replacing Fuel Filter Element
Every 200 hours: Replace fuel filter element.
1. Remove the top cap (Figure 39) from the fuel filter and
rinse cap and filter bowl with diesel fuel.
2. Remove element, and rise with diesel fuel.
3. Reinstall fuel filter and connect fuel lines.
Figure 39. Fuel Filter Disassembly
4. Inspect all fuel lines every 50 hours.
TLG8SSK4F PORTABLE GENERATOR• OPERATION AND PARTS MANUAL — REV. #0 (06/21/16) — PAGE 35
Radiator
Check Daily: Always check the level of the coolant in the
radiator before starting the engine. Remove the radiator
cap and verify that the coolant reaches top of radiator coils.
1. DO NOT remove the radiator cap while the coolant is
hot. The possibility exists of severe burns or scalding
from the coolant gushing out. Let the coolant cool
before removing radiator cap.
2. Check coolant in the reserve tank daily (Figure 40).
Make sure the level is between the FULL (H) and LOW
(L) markings. Fill reserve tank with a mixture of 50/50
antifreeze/water.
Figure 40. Radiator/Reserve Tank
Flushing Out Radiator and Replacing Coolant
1. Remove radiator coolant plug (Figure 41) located at the
bottom of the generator enclosure and drain radiator
coolant. Open the radiator cap while draining. Remove
the overflow tank and drain.
COOLANT DRAIN
PLUG
Figure 41. Coolant Drain Plug
MAINTENANCE
COOLANT DRAIN
OIL DRAIN

Advertisement

Table of Contents
loading