18. Frame Ground Lug — Connect a ground strap
between this lug and a ground rod. Make sure that the
ground rod is inserted deep into the ground to provide
a good earth ground. Consult with local Electrical and
Safety Codes for proper connection based on condition
of use.
19. Ground Terminal — Used to connect external
equipment ground so that the GFCI receptacle will
have a ground path.
20. 240V 3Phase Output terminals(4Wire) — It will
provide 240V, 60 Hz output at 18 amps.
21. Duplex Receptacles — NEMA 5-20R receptacle
provides 120V, 60 Hz output at 20 amps.
22. 20 Amp Breaker (3-phase) — 3-pole, 20 Amp circuit
breaker protects the generator from short circuiting or
overloading When starting the generator, always have
this circuit breaker placed in the "OFF" position.
23. 20 Amp Breaker (for 5-20R) — Single-pole, 20 Amp
circuit breaker protects the 120V duplex receptacle.
When starting the generator, always have this circuit
breaker placed in the "OFF" position.
24. Frequency Meter — Indicates the output frequency
in hertz (Hz), normally 60 Hz.
25. AC Ammeter — Indicates the amount of current the
load is drawing from the U terminal of the generator.
PAGE 20 — TLG8SSK4F PORTABLE GENERATOR• OPERATION AND PARTS MANUAL — REV. #0 06/21/16)
23
22
24
WHISPERWATT
7.5kVA AC GENERATOR
1/ON
e
F
32
F
OFF
20
PS
E
JET
50 A
AC220V 25kA
QUARTZ
AC CIRCUIT BREAKER
27
G. F. C. I. PROTECTED
AC CIRCUIT BREAKER
FOR 3-PHASE OUTPUT
HOUR METER
E
20
Figure 5. Generator Components (2 of 2)
COMPONENTS (GENERATOR)
26
28
29
25
RUN
STOP
HEAT
HIGH
START
VOLTAGE REGULATOR
LOW
STARTER SWITCH
ENGINE SPEED
DECREASE
INCREASE
SWITCH
26. AC Voltmeter — This voltmeter indicates the output
voltage present at the U and V Output Terminal Lugs.
27. Hour Meter — Indicates number of hours the machine
has been in use or hours the engine was run.
28. Engine Speed Switch — This switch controls the
speed of the engine (low/high).
29. Warning Lamp Display — Lights red when the
following conditions occur:
„ Oil Pressure Lamp — If the oil pressure drops
suddenly, the oil pressure lamp will go on, and
the generator will shut down.
„ Charge Lamp — The charge lamp will go on
when loss of engine alternator charge exists and
the generator will shut down.
„ Water Temperature Lamp — The water
temperature lamp will go on if the temperature
rises to an abnormally high level, and the
generator will shut down.
30. Starter Switch — With key inserted, turn clockwise
to start engine.
31. Voltage Regulator Control — Allows ± 15% manual
adjustment of the generator's output voltage.
32. Fuel Gauge — Indicates the amount of fuel in the
fuel tank.
30
31
21
19
18