6.33.8 Control mode for low current
: Low current detection hysteresis width
: Low current trip selection
: Low current detection current
: Low current detection time
• Function
If the current is lower than level and passes for a time longer than , the inverter trips.
Trip information is displayed as "."
=: No tripping (Failure signal FL deactivated).
A low current alarm can be put out by setting the output terminal function selection parameter.
=: The inverter will trip (the failure signal FL will be activated) if a current below the current set with
flows for the period of time specified with .
Title
Low current detection hysteresis width
Low current trip selection
Low current detection current
Low current detection time
<Example of operation>
Output terminal function: 26 (UC) Low current detection
= (No trip)
Ex.) When outputting low current detection signals through output terminal OUT1
Title
Output terminal function selection 1(OUT1)
Note: To put out signals to the terminal OUT2, select the parameter .
Low current
signal output
Output current [%]
+
When = (tripping), the inverter will trip if low current lasts for the period of time set with .
After tripping, the low current signal remains ON.
Function
Function
less than
F-57
Adjustment range
~ %
: No trip
:Trip
~ %
~ sec.
Adjustment range
~
OFF
Time [sec]
E6581528
Default setting
6
Example of setting
ON
OFF