Installer Configuration Menu

Table 5: Installer Configuration Menu (Part 1 of 8)
Parameter
Description and Default
Appearing
on Display
Pswrd
Sets the protective access
password to prevent unauthorized
access to the Installer Configuration
Menu.
Default: 0
Note: The default setting does not
lock out access to the Installer
Configuration Menu.
BI1
Configuration of Binary Input 1.
Default: None
BI2
Configuration of Binary Input 2.
Default: None
TEC22x6(H)-4 and TEC22x6H-4+PIR Series L
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Selection Options
Range: 0 to 1,000
(None): No function is associated with an input.
(Rem NSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
(MotionNO*): Temporary occupancy request via a motion detector
input. Contact open = Unoccupied. When the contact closes, the
thermostat goes into the occupied mode for a specified TOccTime.
Once the TOccTime begins, the thermostat remains in the occupied
mode if the contact is open, until the TOccTime expires.
(MotionNC*): Temporary occupancy request via a motion detector
input. Contact closed = Unoccupied. When the contact opens, the
thermostat goes into the occupied mode for a specified TOccTime.
Once the TOccTime begins, the thermostat remains in the occupied
mode if the contact is closed, until the TOccTime expires.
(Window): Cancels the thermostat heating or cooling action when a
window is open. The fan operation is only affected if the Fan Menu
parameter is set to (4): On-Auto and Auto is the selected fan mode.
A Window alarm appears, indicating that the window needs to be
closed to resume heating or cooling.
*These settings disable any local override function.
(None): No function is associated with an input.
(Door Dry): Door contact only has an effect if BI1 is set to MotionNO
or MotionNC. (See the BI1 parameter in this table.) The occupancy
is now dictated via BI1 and BI2. Any motion detected sets the zone
to Occupied status. The zone remains permanently in occupied
mode until the door contact switch opens momentarily. The
thermostat then enters stand-by mode. If more movements are
detected, the occupied mode resumes. While the door is opened,
any movements detected by the remote PIR sensor or the PIR
accessory cover are ignored. Use a Normally Closed contact
switching device. Contact opened = Door opened,
Contact closed = Door closed.
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(Service): A Service alarm is displayed on the thermostat when the
input is energized. This input can be tied into the air conditioning unit
control card, which provides an alarm should there be a malfunction.
W
® Network Thermostat Controllers with
ON
ORKS
15