Fujitsu AG * V09LAC Series Service Instruction page 59

Split type room air conditioner
Table of Contents

Advertisement

Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : AG*V09/ 12LAC
[Condition]
Ambient temperature : Indoor 15 - 23degC, Outdoor 2 - 12degC
Amount of refrigerant : Regulation amount
Piping length
: 5m (Difference of elevation 1m)
Power voltage
: 50Hz - 230V
Operating condition
: TEST mode (Heating), Hi-speed Fan, Upward blowoff position, Front blowoff,
Measurement method : High side pressure shall be measured with a pressure gauge from service valve.
Total outdoor electric current shall be measured with a clamp meter from connection cord.
Caution : Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
AG*V09LAC
3.40
15°C
20°C
3.20
23°C
(Indoor ambient temp.)
3.00
2.80
2.60
2.40
2.20
0
2
4
Outdoor ambient temperature (°C)
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AG*V09LAC
5.00
15°C
20°C
4.80
23°C
(Indoor ambient temp.)
4.60
4.40
4.20
4.00
3.80
0
2
4
Outdoor ambient temperature (°C)
1 fan operating, With deodorizing filter
6
8
10
12
6
8
10
12
AG*V12LAC
3.80
15°C
20°C
3.60
23°C
(Indoor ambient temp.)
3.40
3.20
3.00
2.80
2.60
14
0
2
Outdoor ambient temperature (°C)
AG*V12LAC
6.80
15°C
20°C
6.60
23°C
(Indoor ambient temp.)
6.40
6.20
6.00
5.80
5.60
5.40
5.20
14
0
2
Outdoor ambient temperature (°C)
08-04
4
6
8
10
12
4
6
8
10
12
14
14