Fujitsu AG * V09LAC Series Service Instruction page 57

Split type room air conditioner
Table of Contents

Advertisement

Outdoor Unit Low Pressure Value and Outdoor Total Electric Current Curve (Cooling)
Model Name : AG*V09/ 12LAC
[Condition]
Ambient temperature : Indoor / Outdoor - Same temperature
Amount of refrigerant : Regulation amount
Piping length
: 5m (Difference of elevation 1m)
Power voltage
: 50Hz - 230V
Operating condition
: TEST mode (Cooling), Hi-speed Fan, Upward blowoff position, Front blowoff,
Measurement method : Low side pressure shall be measured with a pressure gauge from service valve.
Total outdoor electric current shall be measured with a clamp meter from connection cord.
Caution : Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Colling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
AG*V09LAC
1.30
Relative Humidity 50%
Relative Humidity 60%
1.20
Relative Humidity 70%
1.10
1.00
0.90
0.80
0.70
17.5
20
22.5
In/outdoor ambient temperature (°C)
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AG*V09LAC
2.20
Relative Humidity 50%
Relative Humidity 60%
2.10
Relative Humidity 70%
2.00
1.90
1.80
1.70
1.60
17.5
20
22.5
In/outdoor ambient temperature (°C)
1 fan operating, With deodorizing filter
25
27.5
30
25
27.5
30
AG*V12LAC
1.30
Relative Humidity 50%
Relative Humidity 60%
1.20
Relative Humidity 70%
1.10
1.00
0.90
0.80
0.70
32.5
17.5
20
In/outdoor ambient temperature (°C)
AG*V12LAC
3.80
Relative Humidity 50%
Relative Humidity 60%
3.60
Relative Humidity 70%
3.40
3.20
3.00
2.80
2.60
32.5
17.5
20
In/outdoor ambient temperature (°C)
08-02
22.5
25
27.5
30
22.5
25
27.5
30
32.5
32.5