Self - diagnosis function and Checking points
Error Indication
Wired remote
Operation
Timer
10°C HEAT
controller
(RED)
(GREEN)
(ORANGE)
0.5 sec
0.5 sec
OFF
7 times
2 times
0.5 sec
OFF
3 times
0.5 sec
0.5 sec
OFF
8 times
4 times
Error
(Protection)
Discharge temperature
The discharge temperature error is activated. > Permanent stop.
error
[Diagnosis Point]
0F
Excessive High
Excessive high pressure protection on cooling mode has been activated.
Pressure Protection
> Compressor, Outdoor Fan : OFF (It releases after 3 minute ST)
on Cooling
[Diagnosis Point]
24
PFC circuit Error
Excessive voltage of DC voltage on PFC circuit in Inverter PCB is detected, or the excessive current in the circuit is detected.
> Permanent stop.
25
[Diagnosis Point]
Check if 2 way valve or 3 way valve is left open.
Heat radiation is blocked (Inlet/Outlet)
Check if Outdoor Fan is defective (does not rotate).
Refrigeration cycle defective. (Refer to after mentioned "Refrigerant cycle diagnosis").
Heat radiation is blocked (Inlet/Outlet)
Check if Outdoor Fan is defective (does not rotate).
Refrigeration cycle defective. (Refer to after mentioned "Refrigerant cycle diagnosis").
Controller PCB defective. (Refer to after mentioned "PFC circuit diagnosis")