Fujitsu AG * V09LAC Series Service Instruction page 60

Split type room air conditioner
Table of Contents

Advertisement

Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : AG*V14LAC
[Condition]
Ambient temperature : Indoor 15 - 23degC, Outdoor 2 - 12degC
Amount of refrigerant : Regulation amount
Piping length
: 5m (Difference of elevation 1m)
Power voltage
: 50Hz - 230V
Operating condition
: TEST mode (Heating), Hi-speed Fan, Upward blowoff position, Front blowoff,
Measurement method : High side pressure shall be measured with a pressure gauge from service valve.
Total outdoor electric current shall be measured with a clamp meter from connection cord.
Caution : Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
AG*V14LAC
3.60
15°C
20°C
3.50
23°C
(Indoor ambient temp.)
3.40
3.30
3.20
3.10
3.00
0
2
4
Outdoor ambient temperature (°C)
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AG*V14LAC
7.50
7.00
6.50
6.00
5.50
15°C
20°C
5.00
23°C
(Indoor ambient temp.)
4.50
0
2
4
Outdoor ambient temperature (°C)
1 fan operating, With deodorizing filter
6
8
10
12
6
8
10
12
14
14
08-05