Outdoor Unit Low Pressure Value and Outdoor Total Electric Current Curve (Cooling)
Model Name : AG*V14LAC
[Condition]
Ambient temperature : Indoor / Outdoor - Same temperature
Amount of refrigerant : Regulation amount
Piping length
: 5m (Difference of elevation 1m)
Power voltage
: 50Hz - 230V
Operating condition
: TEST mode (Cooling), Hi-speed Fan, Upward blowoff position, Front blowoff,
Measurement method : Low side pressure shall be measured with a pressure gauge from service valve.
Total outdoor electric current shall be measured with a clamp meter from connection cord.
Caution : Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Colling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
AG*V14LAC
1.20
Relative Humidity 50%
Relative Humidity 60%
1.10
Relative Humidity 70%
1.00
0.90
0.80
0.70
0.60
17.5
20
22.5
In/outdoor ambient temperature (°C)
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AG*V14LAC
4.20
Relative Humidity 50%
Relative Humidity 60%
4.00
Relative Humidity 70%
3.80
3.60
3.40
3.20
3.00
17.5
20
22.5
In/outdoor ambient temperature (°C)
1 fan operating, With deodorizing filter
25
27.5
30
25
27.5
30
32.5
32.5