Fujitsu AG * V09LAC Series Service Instruction page 29

Split type room air conditioner
Table of Contents

Advertisement

Defrost Flow Chart
The defrosting shall proceed by the integrating operation time and outdoor heat exchanger
temperature as follows.
Compressor integrating
Compressor integrating
operation:
operation:
Over 60 minutes to
Over 20 minutes to
below 240 minutes
below 60 minutes
Outdoor heat exchanger
Outdoor heat exchanger
temperature:
temperature:
Below -9°C
Below -5°C
Heating operation start : Compressor ON
(In case of 1st defrost)
Compressor integrating
operation:
Over 240 minutes
Outdoor heat exchanger
temperature:
Below -3°C
Defrost Indicator:
[Operation lamp]
7 sec ON / 2 sec OFF
Outdoor heat exchanger temperature:
Over 10°C / 16°C
or
Compressor ON time:
Over 15 minutes
(Not defrosted for 10 minutes)
Compressor integrating
operation:
Over 35 minutes to
below 240 minutes
Outdoor heat exchanger
temperature:
Below -6°C
Defrost start
Compressor OFF
Outdoor fan motor OFF
30 sec later four - way valve OFF
36 sec later compressor ON
Defrost end
05-15
(In case of 2nd and later defrost)
Compressor integrating
operation:
Over 240 minutes
Outdoor heat exchanger
temperature:
Below -3°C