Thermistor Abnormality - Daikin FCQ35B7V1 Service Manual

Hide thumbs Also See for FCQ35B7V1:
Table of Contents

Advertisement

Error Codes
Thermistor Abnormality (C4, C5, C9)
2.7
1
Error code
LED indications
3
3
4
Error generation
5
Causes
Checking
thermistors
3–40
The table below describes the two thermistor abnormalities.
Error
Description
C4
Malfunctioning heat exchanger thermistor system.
C5
Malfuncioning gaspipe thermistor system.
C9
Malfunctioning suction air thermistor system.
The table below shows the LED indications.
Operation
Normal
Malfunctioning
The error is generated when during compressor operation:
Thermistor input > 4.96 V, or
Thermistor output < 0.04 V.
The possible causes are:
Malfunctioning connector connection
Malfunctioning thermistor
Malfunctioning PCB
Broken or disconnected wire.
See page 3–56.
HAP (green)
c
c
ESIE05-04
HBP (green)
c
c
Part 3 – Troubleshooting