ESIE05-04
Step
5
Take out the two tie
wraps fixing the anti
sweat tube of header and
thermistor.
(Be sure not to take out
other tie wrap.)
6
Pull out the thermistor
from the insertion pipe.
Thermistor for heating :
The upper one wrapped
with a yellow tape
Thermistor for liquid
pipe :
The lower one without
taping
Part 5 – Disassembly and Maintenance
Procedure
Anti sweat tube
Disassembly and Maintenance
Points
Heat resistance tie wrap is
used. Be sure to use a heat
resistance tie wrap when
installing new thermistor.
∗ Heat resistance tie wrap
Parts No. :1278921
(Drg No. :4SA90202-1)
(S2673)
Replace thermistor as an
ass'y. (Two thermistors are
bound with special heat
resistance tube.)
(S2674)
1
3
5
5
5–65