Word Allocation

1-4-2 Master Word Allocation

64
The Master treats the CQM1-LK501 I/O Link Unit as a SYSMAC BUS Remote
I/O Slave Unit. Words are allocated to the SYSMAC BUS area and specified by
the Master in the same way as other SYSMAC BUS Remote I/O Slave Units. All
words to be used in the SYSMAC BUS area are set using the DIP switch of the
CQM1-LK501 I/O Link Unit as shown in the following figure.
CQM1-LK501 I/O Link
Unit's DIP switch
Example
Corresponds
binary digit
ON = 1, OFF = 0
2
3
4
2
x 0 + 2
x 1 + 2
x 1 = 24
First offset address 24
The first word of the Master's SYSMAC BUS area varies with the model as seen
in the following table.
Model
C200H/C200HS
C200HX/HG/HE
C500 (F)
C1000H (F)
C2000H
CV2000
CV1000
CV500
CVM1
4
2
3
2
2
2
to
each
SYSMAC BUS area first word
Word 200
Word 0
Word 32x (Master base number)
Word 2300 + 32x (Master base number)
Section 1-4
Master's SYSMAC BUS area
0
24
31
Offset address