Specification
3-2

Specifications

General Specifications
Performance Specifications
Item
Input sensors and set
point ranges
Number of control loops
Control output
Control mode
Setting and display accuracy
Hysteresis
Proportional band
Derivative time
Integral time
Control period
Sampling period
Output refresh period
Current consumption
Weight
Dimensions
Dimensions
The general specifications of the CQM1-TC00j/TC10j conform to those of the
CQM1H/CQM1 Series.
Sensors used with
thermocouples
Sensors used with platinum
resistance thermometers
All dimensions are in millimeters.
Specification
CQM1-TC00j K: –200 to 1,300 °C (–300 to 2,300 °F)
CQM1-TC00j J: –100 to 850 °C (–100 to 1,500 °F)
CQM1-TC10j JPt100: –99.9 to 450.0 °C (–99.9 to 800.0 °F)
–99.9 to 450.0 °C (–99.9 to 800.0 °F)
CQM1-TC10j Pt100:
Two (either 1 or 2 loops can be used)
NPN or PNP output with short-circuit protection
Power supply voltage: 24 VDC
Maximum switching capacity: 100 mA per output
Leakage current: 0.3 mA max.
Residual voltage: 3.0 V max.
ON/OFF or advanced PID control (2 degrees of freedom)
CQM1-TC00j: (Process value ±1% or ±3 °C, whichever is
larger) ±1 digit max.
CQM1-TC10j: (Process value ±1% or ±2 °C, whichever is
larger) ±1 digit max.
0.8 °C/°F
40.0 °C/°F
240 s
40 s
20 s
1 s
1 s
220 mA max. at 5 VDC
200 g max.
32 x 110 x 107 mm (W x H x D)
Section 3-2
+10%
/
–15%