Scaling

5-4

Scaling

Settings
Default Values
–9.999 V
192
The setting method of the scaling values is explained below. Refer to 6-1 Scaling
Value Teaching for the method to obtain the scaling values from the teaching
operation.
Scales input values into desired values within a range from –9999 to 9999. X2 –
Y2 and X1 – Y1 must be input (X: input value, Y: corresponding display data).
The X1 value must be different from the X2 value, otherwise the Unit will process
them as an overrange value of B000.
The following are the factory-set scaling values.
X1:
0
X2:
1000
Y1:
0
Y2:
1000
Therefore, if the Unit is operated with the factory-set scaling values with an input
range from 4 to 20 mA, an input of 4 mA will be regarded as 400 and an input of
20 mA will be regarded as 2000. When the input type is "1 to 5 V," an input of 1 V
will be 1000 and that of 5V will be 5000. When the input type is "–9999 to 9999 V,"
an input of 9,999 V will be 9999 and that of –9999 V will be –9999.
The graph below shows the relationship between the actual input values and the
internal data.
(9999)
(5000)
(2000)
(1000)
(400)
–5 V
Display data
(–5000)
(–9999)
Section 5-4
Input value
Input