Connecting Devices; Cpu; G730 Remote Terminal (Slave) - Omron CQM1H series Operation Manual

Hide thumbs Also See for CQM1H series:
Table of Contents

Advertisement

Connecting Devices

1-3

Connecting Devices

1-3-1 CPU

1-3-2 G730 Remote Terminal (Slave)

32
The G730 Interface Unit connects to the following CPUs.
Name
CQM1H-series
CQM1H-CPU11
CQM1H-CPU21
CQM1H-CPU51
CQM1H-CPU61
CQM1-series
CQM1-CPU11-E
CQM1-CPU21-E
CQM1-CPU41-EV1
CQM1-CPU42-EV1
CQM1-CPU43-EV1
CQM1-CPU44-EV1
Note The number of points includes the CPU internal 16 input points (one word).
Therefore, the actual maximum numbers of points usable by the G730 Interface
Unit are 112 points (7 words), 240 points (15 words), and 496 points (31 words)
respectively.
The following G730 Remote Terminals can be connected to a G730 Interface
Unit.
Model
G730-RID04
Relay input (DC)
G730-RIA04
Relay input (AC)
G730-ROC04
Relay output
G730-ROC04-A Relay output (with error detection function)
G730-VID04
DC input, NPN (common +)
G730-VOD04
Transistor output, NPN (common –)
G730-ROC08
Relay output
G730-AOM08
Relay output (power MOS FET)
G730-VID08
DC input, NPN (common +)
G730-VID08-1
DC input, PNP (common –)
G730-VOD08
Transistor output, NPN (common –)
G730-VOD08-1
Transistor output, PNP (common +)
G730-ROC16
Relay output
G730-AOM16
Relay output (power MOS FET)
G730-VID16
DC input, NPN (common +)
G730-VOD16
Transistor output, NPN (common –)
For more information about the G730 Remote Terminal, refer to the G730 I/O
Terminal Catalog (J92).
Model
Max. I/O Points (see note)
256 (16 words)
512 (32 words)
128 (8 words)
256 (16 words)
I/O type
Section 1-3
I/O points
4
8
16

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cqm1 series

Table of Contents