(2) When "Power" switch is "ON"
Power
Status
supply
No.
indicator
output
lamp
4
5
6

3-4-2 Displays and beeps while testing

7
NOT operation in bypass mode.
3-4-3 Displays and beeps during power failure or AC input
error
(1) When "Power" switch is "ON"
8
9
10
NOT operation in bypass mode.
(2) When "Power" switch is "OFF"
11
12
13
14
BA75T/BA100T/BA100R
Battery
Battery
replace
mode
Beep
ment
lamp
lamp
None
None
None
None
Discharging
Intermittent
4-second
Discharging
intervals
Intermittent
1-second
Discharging
intervals
None
Discharging
None
None
None
None
3 Check and start operation
3-4 Interpreting beeps and displays
Charging
Description
"Power" switch is ON.
ON
Operating normally.
Battery charge is low, so
ON
the unit is waiting to
start up.
Operating normally in
ON
ECO mode.
Self-diagnostic test in
OFF
progress.
In Battery Mode due to
power failure or AC
OFF
input error. Output will
stop if Battery Mode
continues.
(Same as above.)
OFF
Battery level is low, so
output will soon stop.
Battery is dead, so
output stopped. (This is
OFF
displayed only for a few
seconds.)
AC input voltage and
(ON)
AC input frequency are
too high.
AC input frequency is
(ON)
too high.
AC input voltage is too
(ON)
low and AC input
frequency is too high.
AC input voltage is too
(ON)
high.
Solution
---
Continue charging the
battery. You can change
the settings with Simple
Shutdown Software.
For details on ECO
mode, refer to "3-1-4
Setting Switch".
---
Perform shutdown
operations for the
connected devices and
stop them.
(Same as above.)
Charge the battery.
Use within the AC input
voltage/frequency range
described in the
specifications.