4 Maintenance and Inspection

For cautions when maintaining the UPS, refer to "Caution (for maintenance)" shown in the
"Safety precautions" of the beginning of this manual.

4-1 Checking the battery

The lead battery used in the unit has a limited lifespan.
(The life varies depending on your storage/use environment and backup frequency.)
The nearer the end of the life is, the more rapidly deterioration proceeds.

4-1-1 Battery life expectancy

(* Not a guaranteed performance)
Ambient temperature
25°C
30°C
35°C
40°C

4-1-2 Self-diagnosis test

This test performs a failure diagnosis on the unit and performs a test to check for battery
deterioration.
Use the procedure below to check whether a circuit failure has occurred inside the unit and
whether battery replacement is required.
There are two, automatic testing and manual testing, in the self-diagnosis test as follows.
■ Automatic testing
The self-diagnosis test is automatically performed at the factory settings, at the following
timing in the state that the UPS is connected to a commercial power source and the charge
of the battery has been completed. User's operation to start the test is unnecessary.
・When the "Power" switch is turned ON from OFF
・Performed with one time per four weeks on the condition that the "Power" switch is ON
When charge of the battery is not completed, the self-diagnosis test is not performed
immediately.
It is performed automatically after the completion of charge.
BA75T/BA100T/BA100R
4 Maintenance and Inspection
Battery life expectancy
5 years
3.5 years
2.5 years
1.7 years
4-1 Checking the battery