PowerSeries - PC1616/PC1832/PC1864
[29]
Auto-Verified Fire: When violated, system will reset all smoke detectors for 20 seconds, then wait 10 seconds for detectors to settle.
If another fire alarm is detected within 60 seconds, the zone will go into alarm immediately
[30]
Fire Supervisory: Instant alarm, system will activate keypad buzzer. A valid user code is required to silence keypad buzzer
[31]
Day Zone: Instant alarm when system is armed, keypad buzzer (no alarm) when system is disarmed
[32]
Instant Stay/Away: Similar to 'Instant' except panel will auto-bypass the zone if Armed in the Stay mode
[35]
24-Hr Bell/Buzzer: Instant alarm when violated, system will activate bell output if armed, keypad buzzer if disarmed
24-Hr Non-Latching Tamper Zone: Instant tamper condition when violated. Active in both the armed and disarmed state
[36]
[37]
Night Zone: Functions like Interior Stay/Away but will remain bypassed if the user presses [][1] to re-activate Stay/Away zones
when armed in the Stay mode
[41]
24 Hr. Carbon Monoxide: This zone type is used with a hardwired CO detector. This zone definition has a distinct bell cadence in the
event of an alarm. The cadence of this alarm is 4 cycles of 100ms on/off pulses, followed by a 5-second pause, and then repeated.
After 4 minutes, the 5-second pause is extended to 60 seconds in duration. The bell is silenced when an access code is entered or the
bell times out (see your Carbon Monoxide instruction sheet for more details)
[81]
24 Hr. Carbon Monoxide (Wireless): This zone type is used with a wireless CO detector. This zone definition has a distinct bell
cadence in the event of an alarm. The cadence of this alarm is 4 cycles of 100ms on/off pulses, followed by a 5-second pause, and then
repeated. After 4 minutes, the 5-second pause is extended to 60 seconds in duration. The bell is silenced when an access code is
entered or the bell times out
[87]
Delayed 24-Hour Fire (Wireless/Addressable): Same as Delayed 24-Hour Fire (Hardwire) but must be used for wireless or address-
able smoke detectors
[88]
Standard 24-Hour Fire (Wireless/Addressable): Same as Standard 24-Hour Fire (Hardwire) but must be used for wireless or
addressable smoke detectors

[005] System Times

After entering Section [005], enter the 2-digit subsection number for the desired partition and program the Entry Delay 1, Entry Delay 2 and Exit
Delay for each active partition on the system. Valid entries are from [001] to [255] (in seconds). Enter subsection [09] to program the Bell Cut-
Off Time. Valid entries are from [001] to [255] (in minutes).

[006] Installer Code

The default Installer Code is [5555] or [555555] if 6-Digit Access Codes is enabled.

[007] Master Code

The default Master Code is [1234] or [123456] if 6-digit Access Codes is enabled.
[008] Maintenance Code
The default Maintenance Code is [AAAA] (not programmed). This code can only be used to arm and disarm partitions.
[009] to [011] PGM Outputs
The PC1616 and PC1832 have two on-board PGM outputs (PGM1 and PGM2). The PC1864 has four on-board PGM outputs (PGM1 to
PGM4). The panel has the capacity for up to 14 PGM outputs (8 additional low-current PGM outputs with PC5208 module, 4 additional
high-current PGM outputs with a PC5204 module).

PGM Output Options:

Option Description
[00]
For Future Use
[01]
Fire and Burglary: Output will activate (steady for burglary, pulsing for fire) if an alarm occurs on the selected partition
For Future Use
[02]
[03]
Sensor Reset: Output will normally be active and deactivate for 5 seconds when a [
an Auto-Verify Fire alarm is detected
[04]
2-Wire Smoke: Configures PGM2 as 2-wire smoke detector input (PGM2 only)
[05]
Armed Status: Output will activate when all of the selected partitions are armed
Ready Status: Output will activate when all the selected partitions are in the Ready state (Ready light ON)
[06]
[07]
Keypad Buzzer Follow: Output will activate and follow the keypad buzzer for the selected partition when the following events
occur: entry delay, door chime, audible exit delay, automatic arming pre-alert, 24-hr Supervisory Buzzer zone alarm
[08]
Courtesy Pulse: Output will activate during entry/exit delay if the selected partition is armed, and will remain active for an addi-
tional 2 minutes after the entry or exit delay expires
[09]
System Trouble: Output will activate when any selected trouble condition is present
][7][2] fire reset command is entered or when
12