Viessmann Vitocrossal 300 Service Manual page 80

Floor mounted, gas-fired condensing boiler with matrix gas burner and lambda pro control
Table of Contents

Advertisement

Troubleshooting
Fault Codes
(continued)
Fault code on display
9A
9B
DO NOT USE
9C
9E
9F
A7
B0
B1
B5
B7
B8
BA
BB
BC
*1 Control mode:
Burner in fault mode: Boiler control requires manual reset before burner can resume operation.
Burner blocked:
80
System behavior*1
No solar DHW heating
Control mode
No solar DHW heating
Control mode
Control mode
Control mode (stays in
factory default setting)
Burner blocked
Control mode (stays in
factory default setting)
Control mode
(factory default setting)
Burner blocked
Burner blocked
Mixing valve regulates to
a supply temperature of
68°F (20°C)
Mixing valve regulates to
a supply temperature of
68°F (20°C)
Control mode without remote
control
Boiler/burner fully operational (fault code must be verified and reset).
If fault cause is corrected, burner resumes operation.
Vitocrossal 300 CU3A 26 to 57 Service
Cause
Collector temperature
sensor & cable
broken
Tank temperature
sensor cable broken
Tank temperature
sensor % cable
broken
No supply rate in
collector circuit or
flow rate too low or
temperature limiter has
responded
Solar control module
faulty
Faulty programming
unit
Flue gas temperature
sensor shorted out
Communication fault;
programming unit
(internal)
Internal fault
Boiler coding card
missing, faulty or
incorrect boiler coding
card
Flue gas temperature
sensor cable broken
Communication fault -
accessory kit for
heating circuit 2 with
mixing valve
Communication error,
extension kit for heating
circuit 3 (with mixing
valve)
Communication error,
remote control Vitotrol
heating circuit 1
(without mixing valve)
Corrective action
Check the sensor & at the
solar control module.
Check temperature sensor at
connection S3 to the Vitosolic
solar control.
Check temperature sensor %
on solar control module.
Check solar circuit
pump and solar circuit.
Acknowledge fault message.
Replace solar control module.
Replace the programming unit.
Check flue gas temperature
sensor (see page 88).
Check connections and
replace programming unit
if required.
Replace the control unit.
Plug in boiler coding card or
replace if faulty.
Check flue gas temperature
sensor (see page 88).
Check extension kit connections
and code.
Check extension kit connections
and code.
Check connections, cable,
coding address "A0" in "Heating
circuit" group and remote
control unit setting.