Viessmann Vitocrossal 300 Service Manual page 62

Floor mounted, gas-fired condensing boiler with matrix gas burner and lambda pro control
Table of Contents

Advertisement

Coding 2
General
(continued)
Coding in the factory setting
94:0
95:0
97:0
98:1
99:0
9A:0
9B:70
9C:20
9F:8
62
Without Open Therm extension
Without Vitocom 100
communication interface
With LON communication
module: The outside
temperature of the sensor
connected to the control unit is
utilized internally
With LON communication
module: Viessmann system
number (in conjunction with
monitoring several systems
via Vitocom 300)
DO NOT ADJUST
DO NOT ADJUST
Set supply temperature for
external demand 158°F (70°C)
Monitoring LON participants.
If a participant fails to respond,
the values specified inside the
control unit will be used after
20 minutes. Only then will a
fault message be issued.
Differential temperature 8 K;
only in conjunction with mixing
valve circuit
Vitocrossal 300 CU3A 26 to 57 Service
Possible change
94:1
With Open Therm extension
(automatic recognition).
95:1
With Vitocom 100 communication
interface (automatic recognition).
97:1
Control unit receives outside
temperature.
97:2
Control unit transmits the outside
temperature to the Vitotronic
200-H.
98:1
System number adjustable from
to
1 to 5.
98:5
--
--
9B:0
Set supply temperature for external
to
demand adjustable from 32 to
9B:127
260°F (0 to 127°C) (limited by
boiler-specific parameters).
9C:0
No monitoring
9C:5
Time adjustable from 5 to 60
to
minutes.
9C:60
9F:0
Differential temperature adjustable
to
from 0 to 40 K.
9F:40
--
--