Viessmann Vitocrossal 300 Service Manual page 61

Floor mounted, gas-fired condensing boiler with matrix gas burner and lambda pro control
Table of Contents

Advertisement

Vitocrossal 300 CU3A 26 to 57 Service
General
(continued)
Coding in the factory setting
79:1
7B:1
7F:1
80:6
81:1
82:0
88:0
8A:175
8F:0
90:36
With LON communication
module: Control unit is fault
manager
With LON communication
module: Control unit transmits
the time
Detached house
A fault message is displayed
if a fault is active for at least
30 seconds
Automatic summer/wintertime
changeover
Operation with natural gas
Temperature display in °C
(Celsius)
Do not adjust.
Operation in the standard menu
and extended menu enabled.
Note: The respective code is
only activated when you
exit the service menu.
Time constant for calculating
the adjusted outside
temperature 6 h
Possible change
79:0
Control unit is not fault manager.
7B:0
Does not transmit time.
7F:0
Apartment building
Separate adjustment of holiday
program and time program for
DHW heating possible.
80:0
Immediate fault message.
80:2
Minimum fault duration until fault
to
message occurs, adjustable from
10 sec to 995 sec; 1 step ≙ 5 sec.
80:199
81:0
Manual summer/wintertime
changeover.
81:2
Use of the radio clock receiver
(automatic recognition).
81:3
With LON communication module:
The control unit receives the time.
82:1
Operation with LPG (only
adjustable if coding address 11:9
has been set).
88:1
Temperature display in °F
(Fahrenheit).
--
8F:1
Operation in standard menu
and extended menu blocked.
Emissions test mode can be
enabled.
8F:2
Operation enabled in the standard
menu and blocked
in the extended menu.
Emissions test mode can be
enabled.
90:1
Fast (low values) or slow (high
to
values) matching of the supply
90:199
temperature, subject to the set
value when the outside
temperature changes;
1 step ≙ 10 minutes.
Coding 2
--
61